Basler-electric BE1-11 Modbus Protocol Manuale Utente Pagina 139

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 186
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 138
9424200774 Rev B 133
BE1-11 Register Table
Name
Description
Group
Register
Type
Bytes
Writable
Unit
Range
Style
49TC
Max
Emergency
Thermal
Capacity
SG3
24552
Float
4
R W
Percent
150 - 1000
M
49TC
Overload
SG3
24554
Float
4
R W
n/a
0.9 - 1.2
M
50-7
Mode
SG0
24556
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
T
50-7
Source
SG0
24558
Uint32
4
R W
n/a
CT1=0
CT2=1
T
50-7
Pickup
SG0
24560
Float
4
R W
Amp
0.5 - 150
T
50-7
Time Delay
SG0
24562
Float
4
R W
Millisecond
0 - 60000
T
50-7
Direction
SG0
24564
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
T
50-7
Mode
SG1
24566
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
T
50-7
Source
SG1
24568
Uint32
4
R W
n/a
CT1=0
CT2=1
T
50-7
Pickup
SG1
24570
Float
4
R W
Amp
0.5 - 150
T
50-7
Time Delay
SG1
24572
Float
4
R W
Millisecond
0 - 60000
T
50-7
Direction
SG1
24574
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
T
50-7
Mode
SG2
24576
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
T
50-7
Source
SG2
24578
Uint32
4
R W
n/a
CT1=0
CT2=1
T
50-7
Pickup
SG2
24580
Float
4
R W
Amp
0.5 - 150
T
50-7
Time Delay
SG2
24582
Float
4
R W
Millisecond
0 - 60000
T
50-7
Direction
SG2
24584
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
T
50-7
Mode
SG3
24586
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
T
50-7
Source
SG3
24588
Uint32
4
R W
n/a
CT1=0
CT2=1
T
50-7
Pickup
SG3
24590
Float
4
R W
Amp
0.5 - 150
T
50-7
Time Delay
SG3
24592
Float
4
R W
Millisecond
0 - 60000
T
50-7
Direction
SG3
24594
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
T
Vedere la pagina 138
1 2 ... 134 135 136 137 138 139 140 141 142 143 144 ... 185 186

Commenti su questo manuale