2-2 BE1-851 Modbus Protocol 9289900992 Rev F
RESISTER TABLE - ORDERED BY REGISTER NUMBER
Holding Read/Write Data
Register Parameter Supported Format Notes
Session Parameters
40001 Exit R W ASC(1) PS
40002-05 Access Password R W ASC(8) PS
40006 Access Request R W BM(16) PS
Template Parameters
40036 Settings Group Selection R W SI
40038 Fault Selection R W SI
40039 Report Selection R W SI
40040 Report Focus R W INT
Global Parameters
40080-83 Global Password R W ASC(8) PW
40084 Global Path R W BM(8) PW
40085-88 Setting Password R W ASC(8) PW
40089 Setting Path R W BM(8) PW
40090-93 Control Password R W ASC(8) PW
40094 Control Path R W BM(8) PW
40095-98 Report Password R W ASC(8) PW
40099 Report Path R W BM(8) PW
Control Parameters
40117 Select Group R W ASC(1)
40118 Operate Group R W ASC(1)
40119 Select Virtual Selector Switch 43 R W ASC(1)
40120 Operate Virtual Selector Switch 43 R W ASC(1)
40121 Select Virtual Selector Switch 143 R W ASC(1)
40122 Operate Virtual Selector Switch 143 R W ASC(1)
40123 Select Virtual Selector Switch 243 R W ASC(1)
40124 Operate Virtual Selector Switch 243 R W ASC(1)
40125 Select Virtual Selector Switch 343 R W ASC(1)
40126 Operate Virtual Selector Switch 343 R W ASC(1)
40135 Select 101 Virtual Breaker Control Switch R W ASC(1)
40136 Operate 101 Virtual Breaker Control Switch R W ASC(1)
40137 Select All Outputs R W ASC(1)
40138 Operate All Outputs R W ASC(1)
40139 Select Output A R W ASC(1)
40140 Operate Output A R W ASC(1)
40141 Select Output 1 R W ASC(1)
40142 Operate Output 1 R W ASC(1)
40143 Select Output 2 R W ASC(1)
40144 Operate Output 2 R W ASC(1)
40145 Select Output 3 R W ASC(1)
40146 Operate Output 3 R W ASC(1)