608 9424200994 Rev N
Figure 356. 46 Time Characteristic Curve
NOTE: Curves are shown as extending farther to the left than they will in practice. Curves stop at pickup
level. For example, if the user selects 5A FLC and a pickup setting of 0.5A, the per-unit pickup is 0.1A.
The BE1-11g will not pick up at less than 0.1 pu I2 for these settings.
Time Curve Characteristics BE1-11g