Basler-electric BE1-11g Manuale Utente Pagina 1

Navigare online o scaricare Manuale Utente per Relé Basler-electric BE1-11g. Basler Electric BE1-11g User Manual Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 672
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 0
INSTRUCTION MANUAL
FOR
BE1-11g
Generator Protection System
Publication: 9424200994
Revision: N Sep-14
Vedere la pagina 0
1 2 3 4 5 6 ... 671 672

Sommario

Pagina 1 - INSTRUCTION MANUAL

INSTRUCTION MANUAL FOR BE1-11g Generator Protection System Publication: 9424200994 Revision: N Sep-14

Pagina 2

viii 9424200994 Rev N Auxiliary Voltage Input Verification - VX and VX 3rd (Fundamental and Third Harmonic) ... 369 Frequency Ver

Pagina 3

88 9424200994 Rev N be specified on the System Parameters, Sensing Transformers screen in BESTCOMSPlus. Refer to the Configuration chapter for more

Pagina 4

9424200994 Rev N 89 Table 29. Logic Inputs and Outputs Name Logic Function Purpose Block Input Disables the 50 function when true Trip Output True wh

Pagina 5

90 9424200994 Rev N Instantaneous Overcurrent (50) Protection BE1-11g

Pagina 6

9424200994 Rev N 91 Breaker Failure (50BF) Protection The breaker failure (50BF) element provides protection and security for the power system agains

Pagina 7

92 9424200994 Rev N Trip The Trip output becomes true if sensed current exceeds the Phase or Ground Pickup setting and the delay time expires in th

Pagina 8

9424200994 Rev N 93 Table 31. Logic Inputs and Outputs Name Logic Function Purpose Block Input Disables the 50BF function when true 50BFI Input Start

Pagina 9

94 9424200994 Rev N Breaker Failure (50BF) Protection BE1-11g

Pagina 10

9424200994 Rev N 95 Inverse Overcurrent (51) Protection Seven inverse overcurrent (51) elements monitor the current applied to the BE1-11g. An elemen

Pagina 11

96 9424200994 Rev N Unbalance Mode Unbalance mode provides unbalanced current protection. Two methods are available to calculate unbalanced current

Pagina 12

9424200994 Rev N 97 Parameter Description Explanation selected curve infinity if allowed to continue below pickup. Has greatest effect on curve shape

Pagina 13

9424200994 Rev N ix Unrestrained Functional Test Procedure ...

Pagina 14

98 9424200994 Rev N To use the 46 curve, the user should determine the K factor of the generator and the continuous (I2)2t rating of the generator

Pagina 15

9424200994 Rev N 99 𝐴𝑐𝑡𝑢𝑎𝑙 𝑃𝑖𝑐𝑘𝑢𝑝 𝐿𝑒𝑣𝑒𝑙 =𝑆𝑒𝑛𝑠𝑖𝑛𝑔 𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝐿𝑒𝑣𝑒𝑙𝑅𝑒𝑠𝑡𝑟𝑎𝑖𝑛𝑡 𝑃𝑖𝑐𝑘𝑢𝑝 𝑆𝑒𝑡𝑡𝑖𝑛𝑔× 51 𝑃ℎ𝑎𝑠𝑒 𝑃𝑖𝑐𝑘𝑢𝑝 𝑆𝑒𝑡𝑡𝑖𝑛𝑔 Equation 8. Restraint Pickup Level

Pagina 16

100 9424200994 Rev N When single-phase voltage sensing is used, only the inverse overcurrent element on the phase with voltage magnitude informatio

Pagina 17

9424200994 Rev N 101 Figure 65. Inverse Overcurrent Settings Screen Table 36. Operational Settings Setting Range Increment Unit of Measure Default

Pagina 18

102 9424200994 Rev N Setting Range Increment Unit of Measure Default C Coefficient 0 to 1 0.00001 C Coefficient 1.00000 N Coefficient 0.5 to 2.5

Pagina 19

9424200994 Rev N 103 Directional Overcurrent (67) Protection The 67 element provides directional supervision for the overcurrent tripping elements. T

Pagina 20

104 9424200994 Rev N The BE1-11g maintains memory voltage for 20 cycles to allow tripping for close in faults. When using memory voltage polarizati

Pagina 21

9424200994 Rev N 105 Table 37. Polarization Settings Setting Range/Purpose Default 67N Polarization Method IG Use Zero Sequence Current Polarization

Pagina 22

106 9424200994 Rev N Internal Constant Purpose Value Ground current (IG) Minimum Ground (IG) current threshold for Current Polarization test 0.50 A

Pagina 23

9424200994 Rev N 107 −=Relay2,Relay1,Relay0,Source2,Source1,Source0,Source2,Source1,Source0,Relay2,Rela

Pagina 24

x 9424200994 Rev N Specifications ...

Pagina 25

108 9424200994 Rev N Figure 67. Directional Overcurrent Relaying For more theory and mathematics of using sequence components for sensing directio

Pagina 26

9424200994 Rev N 109 Phase Current Differential (87) Protection The phase-current differential (87) element monitors the differential current and pro

Pagina 27

110 9424200994 Rev N Figure 68. 87 Phase Differential Protection Functional Block Diagram 0BPhase Current Differential (87) Protection BE1-11g

Pagina 28

9424200994 Rev N 111 Figure 69. Percentage Restrained Differential Characteristic Pickup and Trip The Pickup output occurs first, followed by the Tr

Pagina 29

112 9424200994 Rev N Harmonics The second and fifth harmonic functions check the ratio of the second and fifth harmonic operate current to the fund

Pagina 30

9424200994 Rev N 113 Figure 70. Phase Current Differential Element Logic Block Table 39. Logic Inputs and Outputs Name Function Purpose Block Input

Pagina 31

114 9424200994 Rev N If one of the calculated taps is outside the acceptable range (2 to 20 for 5 ampere units or 0.4 to 4 for 1 ampere units), the

Pagina 32

9424200994 Rev N 115 Figure 71. Phase Current Differential Settings Screen Figure 72. Phase Current Differential Operation Chart Table 41. Operati

Pagina 33

116 9424200994 Rev N Setting Range Increment Unit of Measure Default Flux Balance Pickup 0 or 0.1 to 5 0.01 amps 0 Time Delay 0 to 60,000 varies

Pagina 34

9424200994 Rev N 117 Neutral Current Differential (87N) Protection The neutral current differential (87N) element provides sensitive differential pro

Pagina 35

9424200994 Rev N 1 Introduction The BE1-11g Generator Protection System provides flexible, reliable, and economical protection, control, monitoring,

Pagina 36

118 9424200994 Rev N Pickup Calculations The differential value is calculated as shown in Equation 17 and Equation 18 and displayed in BESTCOMSPlus

Pagina 37

9424200994 Rev N 119 Figure 73. Current-Polarized Directional Scheme for BE1-11g CT Connection Logic Connections Neutral current differential elemen

Pagina 38

120 9424200994 Rev N Operational Settings Neutral current differential element operational settings are configured on the Neutral Current Different

Pagina 39

9424200994 Rev N 121 Phase Differential Protection: Self-Balancing and Split-Phase Configurations (50/51) The BE1-11g can be configured for the prote

Pagina 40

122 9424200994 Rev N Phase Differential Protection: Self-Balancing and Split-Phase Configurations (50/51) BE1-11g

Pagina 41

9424200994 Rev N 123 Power (32) Protection Two power (32) elements monitor three-phase real power (watts). An element can be configured to protect ag

Pagina 42

124 9424200994 Rev N Bus CT Configuration On protection systems equipped with two sets of CTs, the power element can monitor CT circuit 1 or CT cir

Pagina 43

9424200994 Rev N 125 Assuming polarity current and voltage connections as shown in Figure 76, forward power is defined as flowing into the Area EPS a

Pagina 44

126 9424200994 Rev N Logic Connections Power element logic connections are made on the BESTlogicPlus screen in BESTCOMSPlus. The power element logi

Pagina 45

9424200994 Rev N 127 Loss of Excitation - Reverse Var Based (40Q) Protection The loss of excitation - reverse var based (40Q) element monitors total

Pagina 46

2 9424200994 Rev N Features The BE1-11g protection system includes many features for the protection, monitoring, and control of power system equipm

Pagina 47

128 9424200994 Rev N Bus CT Configuration On protection systems equipped with two sets of CTs, the 40Q element can monitor CT circuit 1 or CT circu

Pagina 48

9424200994 Rev N 129 Operational Settings Loss of excitation - reverse var based element operational settings are configured on the Loss of Excitatio

Pagina 49

130 9424200994 Rev N Loss of Excitation - Reverse Var Based (40Q) Protection BE1-11g

Pagina 50

9424200994 Rev N 131 Distance (21) Protection Two distance (21) elements use the calculated impedance of a fault to determine the fault location. The

Pagina 51

132 9424200994 Rev N Trip The Trip output becomes true if a pickup condition exists for the duration of the element Time Delay. In BESTlogicPlus, t

Pagina 52

9424200994 Rev N 133 Figure 84. Distance Settings Screen Table 49. Operational Settings Setting Range Increment Unit of Measure Default Select Del

Pagina 53

134 9424200994 Rev N Distance (21) Protection BE1-11g

Pagina 54

9424200994 Rev N 135 Loss of Excitation - Impedance Based (40Z) Protection The loss of excitation - impedance based (40Z) element implements a two zo

Pagina 55

136 9424200994 Rev N If the pickup condition subsides before the element delay expires, the timer and Pickup output are reset, no corrective action

Pagina 56

9424200994 Rev N 137 Figure 85. Loss of Excitation - Impedance Based Element Logic Block Table 50. Logic Inputs and Outputs Name Logic Function Purp

Pagina 57

9424200994 Rev N 3 Clock The clock is used by the logging functions to timestamp events. BE1-11g timekeeping can be self-managed by the internal cloc

Pagina 58

138 9424200994 Rev N Table 51. Operational Settings Setting Range Increment Unit of Measure Default Mode Disabled, Non-Voltage Control, Voltage C

Pagina 59

9424200994 Rev N 139 Out of Step (78OOS) Protection The Out of Step (78OOS) element detects out-of-step conditions by monitoring the rate of impedanc

Pagina 60

140 9424200994 Rev N Bus CT Configuration On protection systems equipped with two sets of CTs, the 78OOS element can monitor CT circuit 1 or CT cir

Pagina 61

9424200994 Rev N 141 Figure 89. Out of Step Element Logic Block Table 52. Logic Inputs and Outputs Name Logic Function Purpose Block Input Disables

Pagina 62

142 9424200994 Rev N Table 53. Operational Settings Setting Range Increment Unit of Measure Default Mode Disabled or Enabled n/a n/a Disabled Rev

Pagina 63

9424200994 Rev N 143 Resistance Temperature Detector (49RTD) Protection Fourteen resistance temperature detector (49RTD) elements provide over/undert

Pagina 64

144 9424200994 Rev N annunciate the condition and to initiate corrective action. If a target is enabled for the element, the BE1-11g will record a

Pagina 65

9424200994 Rev N 145 Figure 92. Resistance Temperature Detector Settings Screen Table 55. Operational Settings Setting Range Increment Unit of Measu

Pagina 66

146 9424200994 Rev N Resistance Temperature Detector (49RTD) Protection BE1-11g

Pagina 67

9424200994 Rev N 147 Analog Input Protection Eight analog input elements monitor external analog input signals when two remote RTD modules are connec

Pagina 68

4 9424200994 Rev N BESTlogicPlus. A user-meaningful label can be assigned to each input and to each state (energized and de-energized) for use in r

Pagina 69

148 9424200994 Rev N Element Blocking The Block input provides logic-supervision control of the element. When true, the Block input disables the el

Pagina 70

9424200994 Rev N 149 Remote Analog Input Metering Analog input metering values are obtained through BESTCOMSPlus by using the Metering Explorer to op

Pagina 71

150 9424200994 Rev N Analog Input Protection BE1-11g

Pagina 72

9424200994 Rev N 151 Synchronizer (25A) The synchronizer (25A) element is available only in styles GxxxxxxxSxxxxx and GxxxxxJxTxxxxx of the BE1-11g a

Pagina 73

152 9424200994 Rev N Table 58. Common System and Sensing Transformer Combinations Phase VT Connection Phase Rotation Aux VT Connection Secondary Ph

Pagina 74

9424200994 Rev N 153 Frequency Correction Generator frequency correction is defined by the Slip Frequency setting and further refined by the Breaker

Pagina 75

154 9424200994 Rev N For the phase voltage input, if the connection is three-phase, 3W or 4W, all three phases are tested and must be above the liv

Pagina 76

9424200994 Rev N 155 • In Anticipatory mode: o Breaker Close Time setting must be set above zero (0) • In PLL mode: o Max Slip setting must be se

Pagina 77

156 9424200994 Rev N Figure 97. Synchronizer Element Logic Block Table 59. Logic Inputs and Outputs Name Logic Function Purpose Block Input Disab

Pagina 78

9424200994 Rev N 157 Name Logic Function Purpose Angle Synced Output When in PLL mode, true when the angle between the sources is less than the Break

Pagina 79

9424200994 Rev N 5 General Status Reporting The BE1-11g provides extensive general status reporting for monitoring, commissioning, and troubleshootin

Pagina 80

158 9424200994 Rev N Setting Range Increment Unit of Measure Default Voltage Source > Volt Dest Disabled or Enabled n/a n/a Disabled Freq S

Pagina 81

9424200994 Rev N 159 Virtual Control Switches (43) Five virtual control switch (43) elements provide manual control, locally and remotely, without us

Pagina 82

160 9424200994 Rev N 59N CUTOFF. The closed position of the switch may be labeled DISABLD and the open position may be labeled NORMAL. Control of V

Pagina 83

9424200994 Rev N 161 A Block Tag alarm indicates when a block tag is in place. Refer to the Alarms chapter for information on how to program alarms.

Pagina 84

162 9424200994 Rev N Figure 101. Virtual Control Switches Settings Screen Table 62. Operational Settings Setting Range Increment Unit of Measure D

Pagina 85

9424200994 Rev N 163 Logic Timers (62) Eight logic timer (62) elements emulate virtually any type of timer used in power system applications. The eig

Pagina 86

164 9424200994 Rev N Figure 103. One-Shot/Non-Retriggerable Mode One-Shot/Retriggerable Mode The one-shot retriggerable timer starts its timing se

Pagina 87

9424200994 Rev N 165 time delay for the output to change to false if it is presently true and the initiate input becomes false and stays false. In th

Pagina 88

166 9424200994 Rev N Block input to the desired logic in BESTlogicPlus. When the element is initially selected from the Elements view, the default

Pagina 89

9424200994 Rev N 167 Table 64. Operational Settings Setting Range Increment Unit of Measure Default Mode Disabled, Pickup/Dropout, One-Shot/Non-Retri

Pagina 90

6 9424200994 Rev N Vector Jump (78) Protection One vector jump protection element protects the generator by disconnecting it from the grid when a l

Pagina 91

168 9424200994 Rev N Logic Timers (62) BE1-11g

Pagina 92

9424200994 Rev N 169 Lockout Functions (86) Two lockout function (86) elements can be used to prevent operation of circuit breakers or other devices

Pagina 93

170 9424200994 Rev N Table 66. Operational Settings Setting Range Increment Unit of Measure Default Mode Disabled or Enabled n/a n/a Disabled Retri

Pagina 94

9424200994 Rev N 171 Breaker Control Switch (101) The breaker control switch (101) element provides manual control of a circuit breaker or switch wit

Pagina 95

172 9424200994 Rev N 1. Use the Metering Explorer to open the Control/Breaker Control Switch tree branch (Figure 114). 2. Click on either the TRI

Pagina 96

9424200994 Rev N 173 Figure 115. Breaker Control Element Logic Block Table 67. Logic Inputs and Outputs Name Logic Function Purpose Trip Input Sets

Pagina 97

174 9424200994 Rev N Breaker Control Switch (101) BE1-11g

Pagina 98

9424200994 Rev N 175 Setting Groups Four setting groups allow for adapting the coordination settings to optimize them for a predictable situation. Se

Pagina 99

176 9424200994 Rev N Discrete Inputs When the setting group selection function block is enabled for Discrete Inputs, there is a direct correlation

Pagina 100 - Logic Connections

9424200994 Rev N 177 Figure 118. Input Control Binary Inputs CT Source The CT Source setting configures the setting group selection function to moni

Pagina 101 - Operational Settings

9424200994 Rev N 7 Power (32) Protection Two directional power elements are included in the BE1-11m and can be set for forward or reverse, overpower

Pagina 102

178 9424200994 Rev N to an alternate setting group that can accommodate the condition. The BE1-11g can be set to alarm for this condition using the

Pagina 103 - Element Operation

9424200994 Rev N 179 Figure 119. Setting Group Logic Block Table 70. Logic Inputs and Outputs Name Logic Function Purpose Automatic Input True when

Pagina 104

180 9424200994 Rev N Figure 120. Setting Group Setup Screen Table 71. Operational Settings Setting Range Purpose Default Mode Disabled Discrete In

Pagina 105

9424200994 Rev N 181 Setting Range Purpose Default Monitor Setting Disable, IP, IG, I2, 3I0, 60FL Determines when automatic setting group changes occ

Pagina 106

182 9424200994 Rev N Setting Groups BE1-11g

Pagina 107

9424200994 Rev N 183 Metering The BE1-11g measures the voltage and current inputs, displays those values in real time, records those values every qua

Pagina 108

184 9424200994 Rev N Table 72. Explanation of Figure 122 Call-Outs Call-Out Explanation A Holding the left mouse button down on a metering tab and

Pagina 109

9424200994 Rev N 185 Figure 123. Analog Metering, Voltage Screen Current - Primary and Secondary Metered current includes primary and secondary phas

Pagina 110 - Pickup and Trip

186 9424200994 Rev N Reactive Power Reactive power is metered over a range of −7,500 kilovars to +7,500 kilovars on five ampere nominal systems. On

Pagina 111 -

9424200994 Rev N 187 Figure 126. Analog Metering, Frequency Screen Synchronization Slip Frequency, Slip Angle, and Voltage Difference are metered. S

Pagina 113

8 9424200994 Rev N Breaker Control Switch (101) Tripping and closing of a selected breaker can be controlled by the virtual breaker control switch.

Pagina 114

188 9424200994 Rev N Figure 128. Analog Metering, Differential Screen Energy Energy is metered for positive and negative watthours and varhours. W

Pagina 115

9424200994 Rev N 189 Figure 129. Analog Metering, Energy Screen Click the Edit button to change the values. The Meter Energy Editor screen appears a

Pagina 116

190 9424200994 Rev N Figure 132. Analog Metering, Analog Outputs Screen RTD Meter Figure 133 illustrates the RTD Meter screen. Temperatures are di

Pagina 117

9424200994 Rev N 191 Sequence of Events A sequence of events recorder (SER) report is very useful in reconstructing the exact sequence and timing of

Pagina 118

192 9424200994 Rev N Figure 134. Sequence of Events Screen Viewing SER Data through the Web Page Interface Sequence of events summary can be viewe

Pagina 119

9424200994 Rev N 193 Fault Reporting The fault reporting function records and reports information about faults that have been detected by the BE1-11g

Pagina 120

194 9424200994 Rev N Table 75. Targets as Displayed Target Description 21-#-AB Distance, AB 21-#-BC Distance, BC 21-#-CA Distance, CA 24 Overexcita

Pagina 121

9424200994 Rev N 195 Target Description 59X-#-3V0 Auxiliary Overvoltage, 3V0-3ph VT 59X-#-V1 Auxiliary Overvoltage, Positive-Sequence 59X-#-V2 Auxili

Pagina 122

196 9424200994 Rev N Retrieving Target Information and Resetting Targets To view targets at the front-panel display, navigate to Metering > Stat

Pagina 123

9424200994 Rev N 197 BE1-11g protection systems have three identification fields: Device ID, Station ID, and User ID. These fields are used in the he

Pagina 124

9424200994 Rev N 9 Figure 1. Style Chart BE1-11g Introduction

Pagina 125

198 9424200994 Rev N Viewing and Downloading Fault Data through the Web Page Interface Fault report data can be viewed through the web page interfa

Pagina 126

9424200994 Rev N 199 o If the pickup or logic expressions stay true for more than 60 seconds, an alarm bit in the programmable alarm function is set

Pagina 127

200 9424200994 Rev N All channels are recorded (IA, IA Circuit 2, IB, IB Circuit 2, IC, IC Circuit 2, IG, IG Circuit 2, VA, VB, VC, VX, FP, FX, Ana

Pagina 128

9424200994 Rev N 201 Line Length describes the power line parameters for which distance is to be computed over. The parameters should be entered in u

Pagina 129

202 9424200994 Rev N Protective Fault Analysis Figure 142. Protective Fault Analysis Protective element picks upProtective element tripsBreaker a

Pagina 130

9424200994 Rev N 203 Table 78. Legend for Figure 142 Locator Description A A fault summary report and an oscillograph record are triggered when the P

Pagina 131

204 9424200994 Rev N Fault Reporting BE1-11g

Pagina 132

9424200994 Rev N 205 Alarms The BE1-11g monitors internal systems, external interfaces, and power system equipment and annunciates an alarm when one

Pagina 133

206 9424200994 Rev N Name Description Fuse Loss One or more phases of voltage lost I2 Demand Negative-sequence current unbalance demand IG Demand G

Pagina 134

9424200994 Rev N 207 Name Description S Demand Apparent power (VA) demand maximum exceeded Setting Change Setting change made by user Settings Group

Pagina 135

10 9424200994 Rev N Introduction BE1-11g

Pagina 136

208 9424200994 Rev N under Alarm Configuration. When active, the label of a user alarm is displayed on the Alarms screen on the front-panel display

Pagina 137

9424200994 Rev N 209 Reset will reset all logic alarms. Use the drag-and-drop method to connect a variable or series of variables to the Reset input.

Pagina 138

210 9424200994 Rev N Alarms BE1-11g

Pagina 139

9424200994 Rev N 211 Differential Reporting The BE1-11g records information about the phase current differential (87) status of the BE1-11g and creat

Pagina 140

212 9424200994 Rev N Differential Reporting BE1-11g

Pagina 141

9424200994 Rev N 213 Breaker Monitoring Breaker monitoring helps manage equipment inspection and maintenance expenses by providing extensive monitori

Pagina 142

214 9424200994 Rev N edit this value at the front-panel display. To view the breaker status using BESTCOMSPlus, use the Metering Explorer to open t

Pagina 143

9424200994 Rev N 215 Figure 150. Protective Fault Analysis Protective element picks upProtective element tripsBreaker auxiliary contact changes sta

Pagina 144

216 9424200994 Rev N Table 81. Legend for Figure 150 Locator Description A A fault summary report and an oscillograph record are triggered when the

Pagina 145

9424200994 Rev N 217 Figure 151. Breaker Monitoring Screen To connect the Block logic input, use the Settings Explorer within BESTCOMSPlus to open t

Pagina 146

9424200994 Rev N 11 Quick Start This chapter provides basic installation and setup information about the BE1-11g Generator Protection System. BE1-11g

Pagina 147

218 9424200994 Rev N be read or changed through the communication ports using BESTCOMSPlus. Use the Metering Explorer to open the Reports, Breaker

Pagina 148

9424200994 Rev N 219 Demands Demand recording promotes the ability of an electric power provider to plan for future upgrades. For example, increasing

Pagina 149

220 9424200994 Rev N Setting Range Increment Unit of Measure Default Phase Current Threshold 0 or 0.5 to 16 0.01 amps 0 Neutral/Ground Current Th

Pagina 150

9424200994 Rev N 221 Figure 155. Demand Current Screen Figure 156. Demand Power Screen Refer to the BESTnet™Plus chapter for information on viewing

Pagina 151

222 9424200994 Rev N Demands BE1-11g

Pagina 152

9424200994 Rev N 223 Load Profile The load profile recording function provides a running average of the demand and helps a customer determine when po

Pagina 153

224 9424200994 Rev N Load Profile BE1-11g

Pagina 154

9424200994 Rev N 225 Power Quality The BE1-11g offers class B power quality measurement performance as defined by IEC 610004-30. Power quality data c

Pagina 155

226 9424200994 Rev N Voltage Figure 159 illustrates the Power Quality, Voltage screen. Figure 159. Power Quality, Voltage Screen 10-Second Frequen

Pagina 156

9424200994 Rev N 227 Figure 161. Power Quality, Dip/Swell Screen Harmonics Figure 162 illustrates the Power Quality, Harmonic Voltage screen. The Ha

Pagina 157

12 9424200994 Rev N Table 1. System Recommendations for BESTCOMSPlus and the .NET Framework System Type Component Recommendation 32/64 bit Processo

Pagina 158

228 9424200994 Rev N Power Quality BE1-11g

Pagina 159

9424200994 Rev N 229 Trip Circuit Monitor (52TCM) A trip circuit monitor (52TCM) element continually monitors the circuit breaker trip circuit for vo

Pagina 160

230 9424200994 Rev N Figure 163. Trip Detector Circuit (J Type Case) Table 88. Current Draw for each Power Supply Voltage Rating (J Type Case) Pow

Pagina 161

9424200994 Rev N 231 Figure 164. Trip Detector Circuit (H or P Type Case) Table 89. Current Draw for each Power Supply Voltage Rating (H or P Type C

Pagina 162

232 9424200994 Rev N Figure 165 illustrates typical trip circuit monitor connections for the BE1-11g. Figure 165. Trip Circuit Voltage and Continu

Pagina 163

9424200994 Rev N 233 Figure 166. TCM with Other Devices Trip Circuit Monitor (52TCM) Enable/Disable Jumper (J Type Case) Note A BE1-11g in a J type

Pagina 164

234 9424200994 Rev N Figure 167. Trip Circuit Monitor Enable/Disable Jumper Location Logic Connections Trip circuit monitor logic connections are

Pagina 165

9424200994 Rev N 235 Operational Settings Trip circuit monitor element operational settings are configured on the Trip Circuit Monitor (52TCM) settin

Pagina 166

236 9424200994 Rev N Trip Circuit Monitor (52TCM) BE1-11g

Pagina 167

9424200994 Rev N 237 Fuse Loss (60FL) The fuse loss (60FL) element detects fuse loss or loss of potential in a three-phase system. Element logic conn

Pagina 168

9424200994 Rev N 13 Figure 2. Front Panel Label Example Connect rear terminals A6, A7, and A8 (ground) to a power supply. Figure 3 shows the rear te

Pagina 169

238 9424200994 Rev N Table 92. Fuse Loss Logic Parameters Input True Condition A Positive-sequence volts greater than 8.8% of the nominal voltage;

Pagina 170

9424200994 Rev N 239 Programmable Alarm The BE1-11g indicates an alarm condition when the 60FL element detects a fuse loss or loss of potential. The

Pagina 171

240 9424200994 Rev N Setting Purpose Block V2 Voltage Elements All functions that use the negative-sequence voltage (V2) measurement are blocked wh

Pagina 172

9424200994 Rev N 241 BESTnet™Plus BE1-11g Generator Protection Systems with an Ethernet port have a web page interface that can be used to view BE1-1

Pagina 173

242 9424200994 Rev N Figure 175. Real Time Data Page Demand Data Figure 176 illustrates the Demand Data page. Present and peak demand values are s

Pagina 174

9424200994 Rev N 243 Figure 176. Demand Data Page Faults Fault Summary Figure 177 illustrates the Fault Summary page. To view fault details and down

Pagina 175

244 9424200994 Rev N Figure 177. Fault Summary Page Fault Details Figure 178 illustrates the Fault Details page. Use the buttons to download oscil

Pagina 176

9424200994 Rev N 245 Sequence of Events Figure 179 illustrates the Sequence of Events Summary page. A summary of the sequence of events is shown on t

Pagina 177

246 9424200994 Rev N Figure 180. Power Quality Page BESTnet™Plus BE1-11g

Pagina 178

9424200994 Rev N 247 Mounting BE1-11g protection systems are available in two case configurations. J-option protection systems are supplied in a non-

Pagina 179

14 9424200994 Rev N Figure 4. PWR Rear Terminals (H or P Type Case) Start BESTCOMSPlus® and Activate BE1-11 Plugin To start BESTCOMSPlus, click th

Pagina 180

248 9424200994 Rev N Figure 182. J Type Case - Side Dimensions 7.91 [201.03]6.26 [159.08]1.03 [26.15]0.62 [15.62]0.41 [10.31]0.30 [7.68]8.41 [2

Pagina 181

9424200994 Rev N 249 Case cutout and drilling dimensions are shown in Figure 183. Figure 183. J Type Case - Cutout and Drilling Dimensions 3.03 (

Pagina 182

250 9424200994 Rev N An adapter plate to mount a J case in a GE S2 or ABB FT-21 cutout is shown in Figure 184. Order Basler part number 9108551021.

Pagina 183

9424200994 Rev N 251 An adapter plate to mount a J case in a ABB FT-31/FT-32 cutout is shown in Figure 185. Order Basler part number 9108551022. Fig

Pagina 184

252 9424200994 Rev N An adapter plate to mount a J case in a GE M1/M2 cutout or Basler M1 cutout is shown in Figure 186. Order Basler part number 9

Pagina 185

9424200994 Rev N 253 A J case retrofit mounting plate for the Multilin 489 consists of two parts. See Figure 187 and Figure 188. Order Basler part nu

Pagina 186

254 9424200994 Rev N Figure 188. Retrofit Mounting Plate (Basler P/N: 9424200073) – Part 2 Mounting BE1-11g

Pagina 187

9424200994 Rev N 255 A pivoting projection-mounting kit for a J case is shown in Figure 189. When installed, this kit provides rear access to connect

Pagina 188

256 9424200994 Rev N Figure 190. H1 Rack-Mount Case Dimensions Mounting BE1-11g

Pagina 189

9424200994 Rev N 257 Figure 191. H1 Panel-Mount Case Dimensions BE1-11g Mounting

Pagina 190

9424200994 Rev N 15 Figure 6. BESTCOMSPlus Splash Screen Figure 7. Communication Pull-Down Menu Figure 8. BE1-11 Connection Screen The BE1-11 plug

Pagina 191

258 9424200994 Rev N Adapter bracket 9289924100 allows a single BE1-11g to be mounted in a 19-inch rack (see Figure 192). A second adapter bracket

Pagina 192

9424200994 Rev N 259 If a single H1 BE1-11g (H style case) is to be rack mounted, the cutout and drilling dimensions of Figure 194 should be used. If

Pagina 193

260 9424200994 Rev N Mounting plate cutout and drilling dimensions for two dovetailed H1 protection systems are shown in Figure 196. Figure 196. D

Pagina 194

9424200994 Rev N 261 Part number 9289900016 is used to panel mount two dovetailed protection systems. Figure 197 gives the cutout and drilling dimens

Pagina 195

262 9424200994 Rev N Dovetailing Procedure Basler H1 cases can be interlocked by means of a tenon and mortise on the left and right sides of each c

Pagina 196

9424200994 Rev N 263 Figure 198. Dovetailing Procedure BE1-11g Mounting

Pagina 197

264 9424200994 Rev N Mounting BE1-11g

Pagina 198

9424200994 Rev N 265 Terminals and Connectors Connections to the BE1-11g are dependent on the application and logic scheme selected by the user. As a

Pagina 199

266 9424200994 Rev N Figure 200. Rear-Panel Connections with Fiber Optic Ethernet (J Type Case) Terminal Blocks J-style cases use two sizes of ter

Pagina 200

9424200994 Rev N 267 Figure 201. Rear-Panel Connections with RJ45 Ethernet (H or P Type Case) Figure 202. Rear-Panel Connections with Fiber Optic E

Pagina 201

16 9424200994 Rev N Programming the BE1-11g This section contains an introduction to BESTCOMSPlus, explains summary screens, and gives an example o

Pagina 202

268 9424200994 Rev N By ANSI convention, current transformer polarity will face away from the protected winding of a transformer, motor, generator,

Pagina 203

9424200994 Rev N 269 Figure 205. Example of Reversed CT Polarity BE1-11g Terminals and Connectors

Pagina 204

270 9424200994 Rev N Terminals and Connectors BE1-11g

Pagina 205

9424200994 Rev N 271 Typical Connections Typical external dc connections for the BE1-11g are shown in Figure 206. Figure 206. Typical External DC C

Pagina 206

272 9424200994 Rev N Typical external ac connections (generator differential) for the BE1-11g are shown in Figure 207. Figure 207. Typical AC Conn

Pagina 207

9424200994 Rev N 273 Typical external ac connections (overall differential) for the BE1-11g are shown in Figure 208. Figure 208. Typical AC Connecti

Pagina 208

274 9424200994 Rev N Three-phase voltage sensing, alternate VT inputs are shown in Figure 209. Figure 209. Three-Phase Voltage Sensing, Alternate

Pagina 209

9424200994 Rev N 275 Single-phase current sensing connections are shown in Figure 210. Figure 210. Single-Phase Current Sensing Connections Note So

Pagina 210

276 9424200994 Rev N Typical Connections BE1-11g

Pagina 211

9424200994 Rev N 277 Power System Applications The following figures show examples of the applications that can be served by the Basler Electric BE1-

Pagina 212

9424200994 Rev N 17 Figure 10. View Drop-Down Button Summary Screens Summary screens provide an overview of the system setup. The legend, located in

Pagina 213

278 9424200994 Rev N Figure 212. One-Line Diagram of High Impedance Grounded Generator Protection with Sequential Trip Power System Applicat

Pagina 214

9424200994 Rev N 279 Figure 213. One-Line Diagram of Low Impedance Grounded Generator Protection with Sequential Trip BE1-11g Power System Ap

Pagina 215

280 9424200994 Rev N Figure 214. One-Line Diagram of Basic High Impedance Grounded Generator Protection Power System Applications BE1-11g

Pagina 216

9424200994 Rev N 281 Figure 215. One-Line Diagram of Basic Low Impedance Grounded Generator Protection BE1-11g Power System Applications

Pagina 217

282 9424200994 Rev N Figure 216. One-Line Diagram of High Impedance Grounded Generator Protection with Differential and Sequential Trip Power S

Pagina 218

9424200994 Rev N 283 BESTCOMSPlus® Software BESTCOMSPlus is a Windows®-based, PC application that provides a user-friendly, graphical user interface

Pagina 219

284 9424200994 Rev N Installation BESTCOMSPlus software is built on the Microsoft® .NET Framework. The setup utility that installs BESTCOMSPlus on

Pagina 220

9424200994 Rev N 285 Connect a USB Cable The USB driver was copied to your PC during BESTCOMSPlus installation and is installed automatically after p

Pagina 221

286 9424200994 Rev N Figure 220. Communication Pull-Down Menu The BE1-11 Connection screen shown in Figure 221 appears. Select USB Connection and

Pagina 222

9424200994 Rev N 287 Figure 222. Device Plugin Requires Activation The Activate Device Plugin pop-up appears. Refer to Figure 223. Figure 223. Acti

Pagina 223

9424200994 Rev N i Preface This instruction manual provides information about the installation and operation of the BE1-11g Generator Protection Syst

Pagina 224

18 9424200994 Rev N Programming Example Changing default logic is sometimes required to match the protection requirements of the system. Additional

Pagina 225

288 9424200994 Rev N Figure 224. Activation Key Email The Get Data button extracts the Device, Email Address, and Activation Key from the Windows

Pagina 226

9424200994 Rev N 289 Figure 226. Processing, Please Wait… Advanced Properties Click the Advanced button on the Connection screen to display the Adva

Pagina 227

290 9424200994 Rev N Menu Item Description Export To File Save settings as a *.csv file Print Print, export, or send a settings file Properties Vie

Pagina 228

9424200994 Rev N 291 Menu Item Description About View general, detailed build, and system information Lower Menu Bar (BE1-11 Plugin) Lower menu bar

Pagina 229

292 9424200994 Rev N • Protection • Control • BESTlogicPlus Programmable Logic Logic setup will be necessary after making certain setting change

Pagina 230

9424200994 Rev N 293 Figure 228. Processing, Please Wait… Printing a Settings File To view a preview of the settings printout, select Print Preview

Pagina 231

294 9424200994 Rev N Figure 230. BESTCOMSPlus Settings Compare Auto Export Metering The auto export metering function automatically exports meteri

Pagina 232

9424200994 Rev N 295 BESTCOMSPlus® Updates Ongoing BE1-11g functionality enhancements may make future BE1-11g firmware updates desirable. Enhancement

Pagina 233

296 9424200994 Rev N BESTCOMSPlus® Software BE1-11g

Pagina 234

9424200994 Rev N 297 BESTlogic™Plus BESTlogicPlus Programmable Logic is a programming method used for managing the input, output, protection, control

Pagina 235

9424200994 Rev N 19 becomes an Off-Page Input. The Trip Bus Off-Page Input in connected to physical Output 1 on the BE1-11g. Therefore, the OUT1 cont

Pagina 236

298 9424200994 Rev N BESTlogic™Plus Composition There are three main groups of objects used for programming BESTlogicPlus. These groups are I/O, Co

Pagina 237

9424200994 Rev N 299 Name Description Symbol Relay Trouble Alarm True when a Relay Trouble alarm is active. Refer to the Alarms chapter for more info

Pagina 238

300 9424200994 Rev N Name Description Symbol Pickup and Dropout Timers Pick Up Timer A pickup timer produces a true output when the elapsed time is

Pagina 239

9424200994 Rev N 301 Elements This group contains elements for the 21, 24, 25, 25A, 27P, 27X, 32, 40Q, 40Z, 43, 49RTD, 50, 50BF, 51, 59P, 59X, 60FL,

Pagina 240

302 9424200994 Rev N Name Description Symbol 32-x Power Protection. Refer to the Power (32) Protection chapter. 40Q Loss of Excitation - Reverse V

Pagina 241

9424200994 Rev N 303 Name Description Symbol 51-x Inverse Overcurrent Protection. Refer to the Inverse Overcurrent (51) Protection chapter. 59P-x Ph

Pagina 242

304 9424200994 Rev N Name Description Symbol 87 Current Differential Protection. Refer to the Current Differential (87) Protection chapter. 87N-1

Pagina 243

9424200994 Rev N 305 Name Description Symbol 43-x Virtual Control Switches. Refer to the Virtual Control Switches (43) chapter. 62-x Logic Timers. R

Pagina 244

306 9424200994 Rev N Name Description Symbol Reporting and Alarms 52TCM Trip Circuit Monitor. Refer to the Trip Circuit Monitor (52TCM) chapter. 6

Pagina 245

9424200994 Rev N 307 Name Description Symbol MAJORALMRST Major Alarm Reset. Refer to the Alarms chapter. MINORALMRST Minor Alarm Reset. Refer to the

Pagina 246

20 9424200994 Rev N Figure 15. BESTlogicPlus Logic Page 2 Figure 16. BESTlogicPlus Logic Page 3 Step 10: In this step, the Pickup output of the 5

Pagina 247

308 9424200994 Rev N Caution Always remove the BE1-11g from service prior to changing or modifying the active logic scheme. Attempting to modify a

Pagina 248

9424200994 Rev N 309 Table 101. Default Function Block Logic Function Purpose BESTlogic™Plus Inputs 50-1 Used for instantaneous phase overcurrent pr

Pagina 249

310 9424200994 Rev N Figure 233. One-Line Drawing for Default Logic BESTlogic™Plus BE1-11g

Pagina 250

9424200994 Rev N 311 Figure 234. Logic Diagram for Default Logic Copying and Renaming Preprogrammed Logic Schemes Copying a saved logic scheme to th

Pagina 251

312 9424200994 Rev N Programming BESTlogic™Plus BESTCOMSPlus is used to program BESTlogicPlus. Using BESTCOMSPlus is analogous to physically attach

Pagina 252

9424200994 Rev N 313 Figure 235. Pickup and Dropout Timer Logic Blocks Offline Logic Simulator The offline logic simulator allows you to change the

Pagina 253

314 9424200994 Rev N files. Refer to Figure 237. For information on Settings Files management, refer the BESTCOMSPlus Software chapter. Figure 237

Pagina 254

9424200994 Rev N 315 A Page Setup icon is also provided on the BESTlogicPlus Programmable Logic toolbar allowing you to select Paper Size, Paper Sour

Pagina 255

316 9424200994 Rev N BESTlogic™Plus BE1-11g

Pagina 256

9424200994 Rev N 317 Communication This chapter describes the connections and settings for BE1-11g communication. In addition to standard USB, RS-485

Pagina 257

9424200994 Rev N 21 Figure 17. BESTlogicPlus Programming OUT4 Step 11: In this step, the Pickup output of the 50-3 element is connected to User Alar

Pagina 258

318 9424200994 Rev N Figure 240. RS-485 DB-37 to BE1-11g Ethernet Setup Located on the rear panel, the optional Ethernet communication port provid

Pagina 259

9424200994 Rev N 319 5. Select Configure, Ethernet from the Communication pull-down menu. If the BE1-11g is connected properly, the Configure Ethern

Pagina 260

320 9424200994 Rev N Note The PC running BESTCOMSPlus software must be configured correctly to communicate with the BE1-11g. The PC must have an IP

Pagina 261

9424200994 Rev N 321 244. Use the drag-and-drop method to connect a variable or series of variables to the input. Refer to the BESTlogicPlus chapter

Pagina 262

322 9424200994 Rev N Figure 246. DNP Settings, Miscellaneous Settings Screen Unsolicited Response Support The Unsolicited Response Support screen

Pagina 263

9424200994 Rev N 323 Figure 248. Default Variations Screen DNP Analog Points Mapping Analog points can be mapped to any of the available analog user

Pagina 264

324 9424200994 Rev N To map a Binary Point to the Binary User Map: 1. Select a binary point in the left-hand column. 2. Click on the Add >>

Pagina 265

9424200994 Rev N 325 Modbus™ Setup Settings for Modbus are made by using the Settings Explorer to open the Communications, Modbus tree branch. Settin

Pagina 266

326 9424200994 Rev N Figure 253. Modbus Mapping Screen Communication BE1-11g

Pagina 267

9424200994 Rev N 327 Security Multiple levels of BE1-11g security give personnel the level of access appropriate for the tasks they routinely perform

Pagina 268

22 9424200994 Rev N Figure 19. BESTlogicPlus Toolbar Step 13: In the Settings Explorer, expand Programmable Outputs, Contact Outputs, and name Out

Pagina 269

328 9424200994 Rev N 2. Enter the username and password of the administrator and then click the Log In button. The default Administrator username

Pagina 270

9424200994 Rev N 329 2. The Login dialog box pops up. See Figure 254. An administrator access level is required to set up port access. Enter the use

Pagina 271

330 9424200994 Rev N Table 108. Settings for Access Control Setting Range Increment Unit Default Access Timeout Delay 10 to 3,600 1 seconds 300 Log

Pagina 272

9424200994 Rev N 331 Timekeeping The BE1-11g provides a real-time clock with capacitor backup that is capable of operating the clock for up to 24 hou

Pagina 273

332 9424200994 Rev N Figure 259. Clock Setup Screen Table 109. Settings for Clock Setting Range Increment Unit Default Time Zone Hour Offset –12 t

Pagina 274

9424200994 Rev N 333 Figure 260. Status, Real Time Clock Screen IRIG Port IRIG time code signal connections are located on the rear panel. When a va

Pagina 275

334 9424200994 Rev N Backup Battery for the Real-Time Clock The backup battery for the real time clock is a standard feature of the BE1-11g. A batt

Pagina 276

9424200994 Rev N 335 Figure 261. Front-Panel Circuit Board, Backup Battery Location BE1-11g Timekeeping

Pagina 277

336 9424200994 Rev N Figure 262. Re-Attaching the Front Cover Battery Replacement Procedure for H or P Style Case Battery access is located on the

Pagina 278

9424200994 Rev N 337 Figure 263. Digital Circuit Board, Backup Battery Location Backup Battery(+) Side UpFrontBE1-11g Timekeeping

Pagina 279

9424200994 Rev N 23 Figure 21. User Programmable Alarms Screen Figure 22. OUT4 and USERALM1 with User-Defined Labels BE1-11g Quick Start

Pagina 280

338 9424200994 Rev N Timekeeping BE1-11g

Pagina 281

9424200994 Rev N 339 Device Information BE1-11g identification labels, firmware version, serial number, and style number are found on the Device Info

Pagina 282

340 9424200994 Rev N Device Info Information about a BE1-11g communicating with BESTCOMSPlus can be obtained on the Device Info screen of BESTCOMSP

Pagina 283

9424200994 Rev N 341 screen in BESTCOMSPlus. The Basler Electric Device Package Uploader screen will appear. See Figure 266. Figure 266. Basler Elec

Pagina 284

342 9424200994 Rev N Device Information BE1-11g

Pagina 285

9424200994 Rev N 343 Configuration BE1-11g inputs consist of three-phase current inputs and ground, three-phase voltage inputs, and one auxiliary vol

Pagina 286

344 9424200994 Rev N VT Connections When four-wire VT connections are used, the BE1-11g measures the three-phase to neutral voltages and calculates

Pagina 287

9424200994 Rev N 345 CBA3VarsVarsVarsVars ++=φ where: XPNPIV ∠−∠=φ For Sensing Type: Three-wire In three-wire sensing mode, the equivalent LN v

Pagina 288

346 9424200994 Rev N Power System Settings The BE1-11g requires information about the power system to provide metering, fault reporting, fault loca

Pagina 289

9424200994 Rev N 347 Settings Power system settings are configured on the Power System settings screen (Figure 268) in BESTCOMSPlus. Setting ranges a

Pagina 290

24 9424200994 Rev N Quick Start BE1-11g

Pagina 291

348 9424200994 Rev N BESTCOMSPlus Navigation Path: Settings Explorer, System Parameters, Sensing Transformers HMI Navigation Path: Settings Explore

Pagina 292

9424200994 Rev N 349 Settings Sensing transformers settings are configured on the Sensing Transformers settings screen (Figure 269) in BESTCOMSPlus.

Pagina 293

350 9424200994 Rev N BESTCOMSPlus Navigation Path: Settings Explorer, System Parameters, Transformer Setup HMI Navigation Path: Settings Explorer,

Pagina 294

9424200994 Rev N 351 Determining the Transformer Connection Parameters Wye and Autotransformer Windings. The transformer connection for a CT input ci

Pagina 295

352 9424200994 Rev N compensate for the ±30°, ±60°, ±90°, ±120°, ±150°, and ±180° phase shifts that are possible in transformers and sensing CT con

Pagina 296

9424200994 Rev N 353 Table 115. CT Input Circuit Settings for Non-transformer or Wye-only Application Transformer Connection CT Input Connection BE1-

Pagina 297

354 9424200994 Rev N Transformer Connection CT Input Connection BE1-11g Settings Compensation Applied TX CT Phase Rotation ZAC WYE ZAC WYE W

Pagina 298

9424200994 Rev N 355 Table 118. CT Input Circuit Settings 3 for Delta/Wye Circuit Applications Transformer Connection CT Input Connection BE1-11g Set

Pagina 299

356 9424200994 Rev N Transformer Connection CT Input Connection BE1-11g Settings Compensation Applied TX CT Phase Rotation DAC DAC DAC DAC W

Pagina 300

9424200994 Rev N 357 Note The CT input circuit settings are used by the auto-tap calculation function to calculate the correct tap adjustment factor

Pagina 301

9424200994 Rev N 25 Controls and Indicators BE1-11g controls and indicators are located on the front panel and include sealed membrane switches, LED

Pagina 302

358 9424200994 Rev N Table 119. Internal Compensation Chart IEC Transformer Setup The IEC setup table is aimed at describing transformers that us

Pagina 303

9424200994 Rev N 359 Figure 274. IEC Transformer Setup Screen Display Units The Display Units screen is shown in Figure 275. System Units This setti

Pagina 304

360 9424200994 Rev N Configuration BE1-11g

Pagina 305

9424200994 Rev N 361 Introduction to Testing The need to test protection systems to confirm performance as designed by manufacturers has always exist

Pagina 306

362 9424200994 Rev N • Setting validation • Proper operation of equipment (main or auxiliary) • Proper alarming (to SCADA) and/or targeting Peri

Pagina 307

9424200994 Rev N 363 BE1-11g Self-Test All internal circuitry and software that affect the BE1-11g core functionality are monitored by the continuous

Pagina 308

364 9424200994 Rev N Introduction to Testing BE1-11g

Pagina 309

9424200994 Rev N 365 Acceptance Testing Although Basler Electric performs detailed acceptance testing on all new protection systems, it is generally

Pagina 310

366 9424200994 Rev N IRIG Verification (if used) Purpose: To verify that the BE1-11g acquires and updates IRIG time and date information. Step 1:

Pagina 311

9424200994 Rev N 367 Step 7: Use the Metering Explorer in BESTCOMSPlus to return to the Control, Output Override screen and click on the Enabled b

Pagina 312

26 9424200994 Rev N Table 2. Front Panel Descriptions (J Type Case) Locator Description A Power Indicator – This green LED lights when operating po

Pagina 313

368 9424200994 Rev N current measurements can also be verified on the Metering > Analog Metering > Current > Current Circuit 2 > Second

Pagina 314

9424200994 Rev N 369 Table 123. Voltage Circuit Verification Values Applied Voltage Measured Voltage Lower Limit Upper Limit 80 volts 79.6 V 80.4 V 1

Pagina 315

370 9424200994 Rev N Step 2: Apply the voltage values listed in Table 124 and verify voltage-measuring accuracy by using the Metering Explorer i

Pagina 316

9424200994 Rev N 371 Commissioning Testing Special precautions should be taken to ensure that all tests are performed with safety as the greatest con

Pagina 317

372 9424200994 Rev N Verify that the selected output has changed state on the Control, Output Override screen of BESTCOMSPlus or the front-panel di

Pagina 318

9424200994 Rev N 373 Protection and Control Function Verification Before placing the BE1-11g in service, the user should ensure that all system ac an

Pagina 319

374 9424200994 Rev N Energy Data and Demand BESTCOMSPlus Navigation Path: Metering Explorer, Demand HMI Navigation Path: Metering Explorer, Demand

Pagina 320

9424200994 Rev N 375 Fault Summary Reports BESTCOMSPlus Navigation Path: Metering Explorer, Reports, Fault Records HMI Navigation Path: Metering Expl

Pagina 321

376 9424200994 Rev N Commissioning Testing BE1-11g

Pagina 322

9424200994 Rev N 377 Periodic Testing Because the BE1-11g has extensive internal test capabilities, periodic testing of the protection system can be

Pagina 323

9424200994 Rev N 27 Figure 24. Front Panel (H or P Type Case) Table 3. Front Panel Descriptions (H or P Type Case) Locator Description A Display – 6

Pagina 324

378 9424200994 Rev N Note If verifying the analog measurement circuits by comparison to independent devices is used, you should ensure that the two

Pagina 325

9424200994 Rev N 379 Overexcitation (24) Test Functional testing is a way to assess this protection system’s suitability for your application. Functi

Pagina 326

380 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Element Mode Enabled Protection, Voltage, Overexcitation Enables 24 function 24

Pagina 327

9424200994 Rev N 381 Step 10: (Optional.) Repeat steps 1 through 9 for the B-phase and C-phase voltage inputs. Step 11: (Optional.) Repeat steps 1

Pagina 328

382 9424200994 Rev N Step 3: All inverse timing tests are based on % of nominal Volts/Hertz (1 PU value). Refer to the Time Curve Characteristic

Pagina 329

9424200994 Rev N 383 Table 131. Definite Time Verification Test Settings Setting Value Description Inverse Time Pickup 0 Disables Inverse Time Pickup

Pagina 330

384 9424200994 Rev N Step Pickup Setting Low Actual Pickup High Low* Actual Dropout High* Pass/Fail 15 2.36 2.31 V/Hz 2.41 V/Hz 2.289 V/Hz 2.336

Pagina 331

9424200994 Rev N 385 Sync-Check (25) Test Functional testing is a way to assess this protection system’s suitability for your application. Functional

Pagina 332

386 9424200994 Rev N Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in Figure 277. • Blocking is disabled. •

Pagina 333

9424200994 Rev N 387 Step 10: Increase the voltage until OUT2 closes (90 volts). Record the result. Step 11: (Optional.) Repeat steps 3 through 10

Pagina 334

ii 9424200994 Rev N 12570 State Route 143 Highland IL 62249-1074 USA www.basler.com [email protected] Tel: +1 618.654.2341 Fax: +1 618.654.2351

Pagina 335

28 9424200994 Rev N Locator Description J Edit Pushbutton – Settings changes are made at the front panel using this pushbutton. When pushed, this s

Pagina 336

388 9424200994 Rev N Table 135. Inverse Time and Definite Time Pickup Test Settings (25) Setting Value Description Voltage Difference 10% Sets volt

Pagina 337

9424200994 Rev N 389 Step Dropout Delay Setting Low Actual Timing High Pass/Fail 6 VTP - Dead V Dropout Delay - 5000 ms 4,968 ms 5,032 ms P / F

Pagina 338

390 9424200994 Rev N Sync-Check (25) Test BE1-11g

Pagina 339

9424200994 Rev N 391 Phase Undervoltage (27P) Test Functional testing is a way to assess this protection system’s suitability for your application. F

Pagina 340

392 9424200994 Rev N Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 279. • Blocking is disabled. •

Pagina 341

9424200994 Rev N 393 Step 2: Prepare to monitor the 27P-1 timings. Timing accuracy is verified by measuring the elapsed time between a sensing volta

Pagina 342

394 9424200994 Rev N Phase Undervoltage (27P) Test BE1-11g

Pagina 343

9424200994 Rev N 395 Auxiliary Undervoltage (27X) Test Functional testing is a way to assess this protection system’s suitability for your applicatio

Pagina 344

396 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Timing Mode Definite Protection, Voltage, Undervoltage (27X-1) Selects definite

Pagina 345

9424200994 Rev N 397 Table 141. Timing Test Settings (3V0 Mode) Pickup Setting Time Delay 65 V 2,000 ms 65 V 5,000 ms 65 V 10,000 ms Step 2: Prepare

Pagina 346

9424200994 Rev N 29 1. Press the Edit pushbutton. 2. Enter the username by pressing the UP or DOWN scrolling pushbuttons until the proper first cha

Pagina 347

398 9424200994 Rev N Figure 281. BESTlogicPlus Settings (V1 Mode) Table 143. Pickup Test Settings (V1 Mode) Pickup Setting Time Delay 78 V 50 ms 3

Pagina 348

9424200994 Rev N 399 Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 144. Record the results. Step 6: (Optional.)

Pagina 349

400 9424200994 Rev N Step 4: Prepare to monitor the 27X-1 function operation. Operation can be verified by monitoring OUT2 (see Figure 282). Step

Pagina 350

9424200994 Rev N 401 Setting Value BESTCOMSPlus Screen Description Inhibit Level 10 V Protection, Voltage, Undervoltage (27X-1) Sets inhibit level to

Pagina 351

402 9424200994 Rev N Table 150. Timing Test Settings (Vx Fundamental Mode) Pickup Setting Time Delay 115 V 2,000 ms 115 V 5,000 ms 115 V 10,000 ms

Pagina 352

9424200994 Rev N 403 Figure 284. BESTlogicPlus Settings (Vx Third Harmonic Mode) Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Underv

Pagina 353

404 9424200994 Rev N Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 153. Record the results. Step 6: (Optional

Pagina 354

9424200994 Rev N 405 Timing Verification (V1 Mode) Time Delay Range = 50 to 600,000 ms Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater Ste

Pagina 355

406 9424200994 Rev N Timing Verification (Vx Fundamental Mode) Time Delay Range = 50 to 600,000 ms Timing Accuracy = ±0.5% or ±2 cycles, whichever

Pagina 356

9424200994 Rev N 407 Phase Overvoltage (59P) Test Functional testing is a way to assess this protection system’s suitability for your application. Fu

Pagina 357

30 9424200994 Rev N To operate the switch, use the following procedure: 1. Use the scrolling pushbuttons to scroll to Metering, Control, Virtual S

Pagina 358

408 9424200994 Rev N Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 285. • Blocking is disabled. •

Pagina 359

9424200994 Rev N 409 Step 2: Prepare to monitor the 59P-1 timings. Timing accuracy is verified by measuring the elapsed time between a sensing volta

Pagina 360

410 9424200994 Rev N Phase Overvoltage (59P) Test BE1-11g

Pagina 361

9424200994 Rev N 411 Auxiliary Overvoltage (59X) Test Functional testing is a way to assess this protection system’s suitability for your application

Pagina 362

412 9424200994 Rev N Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 286. • Blocking is disabled. •

Pagina 363

9424200994 Rev N 413 Step 2: Prepare to monitor the 59X-1 timings. Timing accuracy is verified by measuring the elapsed time between a sensing volta

Pagina 364

414 9424200994 Rev N Table 161. Pickup Test Settings (V1 Mode) Pickup Setting Time Delay 82 V 50 ms 42 V 50 ms 25 V 50 ms Step 4: Prepare to monit

Pagina 365

9424200994 Rev N 415 Table 163. Operational Settings (V2 Mode) Setting Value BESTCOMSPlus Screen Description Phase VT Ratio 1 System Parameters, Sens

Pagina 366

416 9424200994 Rev N Step 7: Verify the pickup and dropout accuracy at 120 Vac for a pickup setting of 42 V (126 Vac on test set) and 70 Vac for a

Pagina 367

9424200994 Rev N 417 Figure 289. BESTlogicPlus Settings (Vx Fundamental Mode) Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Overvolta

Pagina 368

9424200994 Rev N 31 Figure 26. Front-Panel Display Setup Screen Table 4. Settings for Front-Panel Display Locator Setting Range Increment Unit Defau

Pagina 369

418 9424200994 Rev N Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 168. Record the results. Step 6: (Optional

Pagina 370

9424200994 Rev N 419 Step 5: Connect and apply a single-phase, 120 Vac, 3rd harmonic voltage source to the Vx input, terminals C17 (polarity) and C1

Pagina 371

420 9424200994 Rev N Timing Verification (3V0 Mode) Time Delay Range = 50 to 600,000 ms Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater

Pagina 372

9424200994 Rev N 421 Step Time Delay Setting Low Actual Timing High Pass/Fail 4 2,000 ms 1,968 ms 2,032 ms P / F 5 5,000 ms 4,968 ms 5,032 ms P

Pagina 373

422 9424200994 Rev N Auxiliary Overvoltage (59X) Test BE1-11g

Pagina 374

9424200994 Rev N 423 Vector Jump (78V) Test Functional testing is a way to assess this protection system’s suitability for your application. Function

Pagina 375

424 9424200994 Rev N Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 291. • Blocking is disabled. •

Pagina 376

9424200994 Rev N 425 Timing Verification Timing Accuracy = 150 ms or less Step Time Delay Actual Timing Pass/Fail 6 150 ms P / F 7 150 ms P /

Pagina 377

426 9424200994 Rev N Vector Jump (78V) Test BE1-11g

Pagina 378

9424200994 Rev N 427 Frequency (81) Test Functional testing is a way to assess this protection system’s suitability for your application. Functional

Pagina 379

32 9424200994 Rev N Controls and Indicators BE1-11g

Pagina 380

428 9424200994 Rev N Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 292. • Blocking is disabled. •

Pagina 381

9424200994 Rev N 429 Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 293. • Blocking is disabled. • O

Pagina 382

430 9424200994 Rev N Step 2: Prepare to monitor the 81-1 timings. Timing accuracy is verified by measuring the elapsed time between a frequency

Pagina 383

9424200994 Rev N 431 Step 3: Prepare to monitor the 81-1 function operation. Operation can be verified by monitoring OUT2 (see Figure 294). Step 4

Pagina 384

432 9424200994 Rev N • Blocking is disabled. • OUT1 closes for 81-1 Trip. • OUT2 closes for 81-1 Pickup. • Fault recording is enabled. Figure

Pagina 385

9424200994 Rev N 433 Underfrequency Pickup Verification Pickup Setting Range = 15 to 70 Hz Pickup Accuracy = ±0.01 Hz Reset = 0.02 Hz ±0.01 Hz of the

Pagina 386

434 9424200994 Rev N Frequency (81) Test BE1-11g

Pagina 387

9424200994 Rev N 435 Instantaneous Overcurrent (50) Test Functional testing is a way to assess this protection system’s suitability for your applicat

Pagina 388

436 9424200994 Rev N Figure 296. BESTlogicPlus Settings (Phase Mode) Step 3: Use BESTCOMSPlus to open the Protection, Current, Instantaneous Ov

Pagina 389

9424200994 Rev N 437 Table 183. Timing Test Settings (Phase Mode) Pickup Setting Time Delay 0.5 A 2,000 ms 0.5 A 5,000 ms 0.5 A 10,000 ms Step 5: Re

Pagina 390

9424200994 Rev N 33 Contact Inputs and Outputs BE1-11g Generator Protection Systems provide up to seven contact inputs, up to eight general-purpose c

Pagina 391

438 9424200994 Rev N Table 185. Pickup Test Settings (3I0 Mode) Sensing Input Type Range Pickup Setting Time Delay 5 A Low 0.5 A 0 ms Middle 5.0

Pagina 392

9424200994 Rev N 439 Pickup Verification (I2 Mode) Step 1: Use BESTCOMSPlus to send the operational settings in Table 187 to the BE1-11g. Reset al

Pagina 393

440 9424200994 Rev N Step 5: Connect a current source to terminals D1 and D2 (A-phase). For a single-phase input test, I2 = Ia / 3. Therefore, the

Pagina 394

9424200994 Rev N 441 Setting Value BESTCOMSPlus Screen Description Element Mode IG Protection, Current, Instantaneous Overcurrent (50-1) Enables 50-1

Pagina 395

442 9424200994 Rev N Step 10: (Optional.) Repeat steps 1 through 9 with CT Circuit 2 as the source for protection systems equipped with two sets o

Pagina 396

9424200994 Rev N 443 Step Time Delay Setting Low Actual Timing High Pass/Fail 4 2,000 ms 1,942 ms 2,058 ms P / F 5 5,000 ms 4,927 ms 5,073 ms P

Pagina 397

444 9424200994 Rev N Dropout should occur between 93-99% of the actual pickup value. Step Pickup Setting Low Actual Pickup High Low* Actual Dropout

Pagina 398

9424200994 Rev N 445 Timing Verification (IG Mode) Time Delay Range = 0 to 60,000 ms Timing Accuracy = ±0.5% or ±½ cycle, whichever is greater + 3 cy

Pagina 399

446 9424200994 Rev N Instantaneous Overcurrent (50) Test BE1-11g

Pagina 400

9424200994 Rev N 447 Breaker Fail (50BF) Test Functional testing is a way to assess this protection system’s suitability for your application. Functi

Pagina 401

34 9424200994 Rev N 1. Remove the BE1-11g from service and de-energize it. 2. The contact-sensing input jumpers are located behind the rear termi

Pagina 402

448 9424200994 Rev N • Fault recording is enabled. • Breaker Status is closed with /IN1. Figure 300. BESTlogicPlus Settings (BFI52 Contact Init

Pagina 403

9424200994 Rev N 449 Setting Value BESTCOMSPlus Screen Description Element Mode IA Protection, Current, Instantaneous Overcurrent (50-1) Enables 50-1

Pagina 404

450 9424200994 Rev N Table 195. Control Time Delay Settings Setting Value BESTCOMSPlus Screen Description Phase Pickup 1 A Protection, Current, Bre

Pagina 405

9424200994 Rev N 451 Inverse Overcurrent (51) Test Functional testing is a way to assess this protection system’s suitability for your application. F

Pagina 406

452 9424200994 Rev N Figure 302. BESTlogicPlus Settings (Phase Mode) Step 3: Use BESTCOMSPlus to open the Protection, Current, Inverse Overcurr

Pagina 407

9424200994 Rev N 453 Step 2: Prepare to monitor the 51-1 timings. Timing accuracy is verified by measuring the elapsed time between a sensing curren

Pagina 408

454 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Source CT Circuit 1 Protection, Current, Instantaneous Overcurrent (51-1) Select

Pagina 409

9424200994 Rev N 455 Timing Verification (3I0 Mode) Step 1: Use BESTCOMSPlus to open the Protection, Current, Inverse Overcurrent (51-1) screen an

Pagina 410

456 9424200994 Rev N Pickup Verification (I2 Mode) Step 1: Use BESTCOMSPlus to send the operational settings in Table 204 to the BE1-11g. Reset

Pagina 411

9424200994 Rev N 457 for a 1 A BE1-11g with a pickup setting of 0.1, it would require 0.1 times 3 or 0.3 amperes of input current. Step 6: Slowly in

Pagina 412

9424200994 Rev N 35 3. Locate the two jumper terminal blocks that are mounted on the Digital Circuit Board. The Digital Circuit Board is the middle

Pagina 413

458 9424200994 Rev N Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3. Step 7: (Optional.) Repeat steps 1 through 6 fo

Pagina 414

9424200994 Rev N 459 Table 209. Pickup Test Settings (IG Mode) Sensing Input Type Range Pickup Setting Time Dial Time Curve 5 A Low 0.5 A 0 I2 Mid

Pagina 415

460 9424200994 Rev N Table 211. Timing Test Settings (IG Mode) Sensing Type Time Dial Applied Current 5 A 0.5 1.00 A 2.50 A 12.50 A 5.0 1.00 A 2.50

Pagina 416

9424200994 Rev N 461 Dropout should occur between 93-99% of the actual pickup value. Step Pickup Setting Low Actual Pickup High Low* Actual Dropout

Pagina 417

462 9424200994 Rev N Dropout should occur between 93-99% of the actual pickup value. Step Pickup Setting Low Actual Pickup High Low* Actual Dropo

Pagina 418

9424200994 Rev N 463 Dropout should occur between 93-99% of the actual pickup value. Step Pickup Setting Low Actual Pickup High Low* Actual Dropout H

Pagina 419

464 9424200994 Rev N Pickup Verification (IG Mode) Pickup Setting Range = 0.5 to 16 A for 5A sensing 0.1 to 3.2 A for 1A sensing 0.01 to 0.8 A

Pagina 420

9424200994 Rev N 465 4 5.0 I2 0.50 A 1.798 sec 1.988 sec P / F 4 5.0 I2 2.50 A 0.944 sec 1.044 sec P / F 4 9.9 I2 0.20 A 8.300 sec 9.173 s

Pagina 421

466 9424200994 Rev N Inverse Overcurrent (51) Test BE1-11g

Pagina 422

9424200994 Rev N 467 Directional Overcurrent (67) Test Functional testing is a way to assess this protection system’s suitability for your applicatio

Pagina 423

36 9424200994 Rev N Figure 29. Digital Input Conditioning Timing Diagram Setting the Contact Inputs BESTCOMSPlus Navigation Path: Settings Explore

Pagina 424

468 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Element Mode IA Protection, Current, Instantaneous Overcurrent (50-1) Enables 50

Pagina 425

9424200994 Rev N 469 zero sequence impedance angles is continuously adjustable between 0 and 90°, the default setting of 80° is used in the test exam

Pagina 426

470 9424200994 Rev N Table 214. Directional, Negative-Sequence Operational Settings Setting Value BESTCOMSPlus Screen Description Pickup 0 A Protec

Pagina 427

9424200994 Rev N 471 Table 216. Directional, Negative-Sequence Polarizing, Neutral Operational Settings Setting Value BESTCOMSPlus Screen Description

Pagina 428

472 9424200994 Rev N sequence line angle. Verify that OUT2 opens at approximately 170 degrees lagging and 350 degrees lagging. OUT2 should remain c

Pagina 429

9424200994 Rev N 473 Zero-Sequence Current Polarization Use setup commands in Table 212. Using Table 218 as a guide, send the settings to the BE1-11g

Pagina 430

474 9424200994 Rev N Directional Overcurrent (67) Test BE1-11g

Pagina 431

9424200994 Rev N 475 Phase Current Differential (87) Test Functional testing is a way to assess this protection system’s suitability for your applica

Pagina 432

476 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description CT 2 Connection WYE System Parameters, Sensing Transformers Sets the CT 2 connec

Pagina 433

9424200994 Rev N 477 Setting Value BESTCOMSPlus Screen Description Mode Percent Differential Protection, Current, Phase Differential (87) Sets the ty

Pagina 434

9424200994 Rev N 37 See Table 6 for a list of settings and their defaults. Table 6. Contact Input Settings Setting Range Increment Unit Default Label

Pagina 435

478 9424200994 Rev N Figure 307. BESTlogicPlus Settings (87R) Step 8: Slowly decrease the A-phase current in CT circuit 1 or 2 until OUT2 closes

Pagina 436

9424200994 Rev N 479 Setting Value BESTCOMSPlus Screen Description Nominal Phase Current 5 A System Parameters, Power System Sets the nominal seconda

Pagina 437

480 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Circuit 1 Tap 2.00 System Parameters, Transformer Setup Sets the tap for circuit

Pagina 438

9424200994 Rev N 481 Step 5: Slowly increase the A-phase current in CT circuit 1 or 2 until OUT2 closes and record the pickup. This should occur at

Pagina 439

482 9424200994 Rev N Unrestrained Functional Test Procedure Pickup Verification Step 1: Use BESTCOMSPlus to verify the operational settings in T

Pagina 440

9424200994 Rev N 483 Second-Harmonic Restraint Verification (Shared) Step 1: Use BESTCOMSPlus to send the operational settings in Table 220 and ve

Pagina 441

484 9424200994 Rev N Functional Test Reports Restrained Pickup Verification (Maximum Restraint) Pickup Accuracy = ±2% or ±0.05A, whichever is great

Pagina 442

9424200994 Rev N 485 2nd Harmonic Restraint Verification (Independent) Pickup Accuracy = ±2% or ±0.05A, whichever is greater. Step Pickup Setting Low

Pagina 443

486 9424200994 Rev N Phase Current Differential (87) Test BE1-11g

Pagina 444

9424200994 Rev N 487 Neutral Current Differential (87N) Test Functional testing is a way to assess this protection system’s suitability for your appl

Pagina 445

9424200994 Rev N iii Contents Introduction ...

Pagina 446

38 9424200994 Rev N BESTlogicPlus expressions for OUT1 through OUT8 and OUTA drive contact outputs OUT1 through OUT8 and OUTA. The state of the con

Pagina 447

488 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Circuit 1 Ground Compensation No System Parameters, Transformer Setup Disables t

Pagina 448

9424200994 Rev N 489 Step 5: Slowly increase the magnitude of the IG current input until OUT2 closes and record the pickup. This should occur at 5.0

Pagina 449

490 9424200994 Rev N Neutral Current Differential (87N) Test BE1-11g

Pagina 450

9424200994 Rev N 491 Power (32) Test Functional testing is a way to assess this protection system’s suitability for your application. Functional test

Pagina 451

492 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description 32-1 A Over Enabled Target Configuration, Targets Enables phase A over target fo

Pagina 452

9424200994 Rev N 493 Step 8: (Optional.) Repeat Steps 1 through 7 for settings group 1, 2, and 3. Step 9: (Optional.) Repeat Steps 1 through 8

Pagina 453

494 9424200994 Rev N Step 4: With the BE1-11g picked up (OUT2 closed), change the angle of the applied current to lag the voltage by 180 degrees

Pagina 454

9424200994 Rev N 495 Step Pickup Setting Low Actual Pickup High Low* Actual Dropout High* Pass/Fail 3 500 W 485 W 515 W 475 W 495 W P / F 5 1,0

Pagina 455

496 9424200994 Rev N Power (32) Test BE1-11g

Pagina 456

9424200994 Rev N 497 Loss of Excitation - Reverse Var Based (40Q) Test Functional testing is a way to assess this protection system’s suitability for

Pagina 457

9424200994 Rev N 39 Programmable Hold Timer—Hold Attribute Historically, electromechanical relays have provided trip contact seal-in circuits. These

Pagina 458

498 9424200994 Rev N Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in Figure 311. • Blocking is disabled. •

Pagina 459

9424200994 Rev N 499 Step 2: Prepare to monitor the 40Q timings. Timing accuracy is verified by measuring the elapsed time between a sensing current

Pagina 460

500 9424200994 Rev N Loss of Excitation - Reverse Var Based (40Q) Test BE1-11g

Pagina 461

9424200994 Rev N 501 Distance (21) Test Functional testing is a way to assess this protection system’s suitability for your application. Functional t

Pagina 462

502 9424200994 Rev N Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 312. • Blocking is disabled. •

Pagina 463

9424200994 Rev N 503 Step 4: Gradually decrease the magnitude all three phase voltages until OUT2 closes. Record the time to trip (OUT1 closes). Ver

Pagina 464

504 9424200994 Rev N Distance (21) Test BE1-11g

Pagina 465

9424200994 Rev N 505 Loss of Excitation – Impedance Based (40Z) Test Functional testing is a way to assess this protection system’s suitability for y

Pagina 466

506 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Phase VT Ratio 1 System Parameters, Sensing Transformers Sets phase VT ratio to

Pagina 467

9424200994 Rev N 507 opens. Reset the target. Impedance values for this test have been converted to measureable phase-neutral voltages. Figure 313.

Pagina 468

40 9424200994 Rev N Figure 34. Contact Outputs Screen Contact Output Logic Override Control BESTCOMSPlus Navigation Path: Metering Explorer, Contr

Pagina 469

508 9424200994 Rev N Step Pickup Setting Low Actual Pickup High Pass/Fail 5 10.0 V (5 Ω) 9.70 V 10.3 V P / F 6 8.00 V 7.92 V 8.08 V P / F

Pagina 470

9424200994 Rev N 509 Out of Step (78OOS) Test Functional testing is a way to assess this protection system’s suitability for your application. Functi

Pagina 471

510 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Element Mode Enabled Protection, Impedance, Out of Step (78OOS) Enables the 78O

Pagina 472

9424200994 Rev N 511 Figure 314. BESTlogicPlus Settings Step 9: Slowly decrease the angles of the voltage inputs to close OUT4 and OUT5 (impedance

Pagina 473

512 9424200994 Rev N Step 7: Set the voltage input angles to A∠180°, B∠60°, C∠300°. Increase the voltage until OUT3 reopens and record the time be

Pagina 474

9424200994 Rev N 513 Synchronizer (25A) Test Functional testing is a way to assess this protection system’s suitability for your application. Functio

Pagina 475

514 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Element Mode PLL Control, Synchronizer (25A) Enables 25A function for PLL opera

Pagina 476

9424200994 Rev N 515 ` Figure 315. BESTlogicPlus Settings 1 (25A) Step 4: Connect a balanced, three-phase voltage source of 69.28 Vpn, 60 Hz to BE

Pagina 477

516 9424200994 Rev N voltage of 69.28 Vpn, ∠0°, to terminals C17 (Vx-phase) and C18 (Vx-neutral). The 25A Slip Diff digital point should be true. S

Pagina 478

9424200994 Rev N 517 Frequency Raise/Lower Continuous Output Verification Step 1: Use BESTCOMSPlus to monitor the status of OUT2 (Lower) and OUT3

Pagina 479

9424200994 Rev N 41 In the Action column, select Pulse from the drop-down menu and click on the green arrow to the right. Pulse override control can

Pagina 480

518 9424200994 Rev N Figure 316. BESTlogicPlus Settings 2 (25A) Functional Test Report - PLL ΔV Accuracy = ±2% or ±1V, whichever is greater. Slip

Pagina 481

9424200994 Rev N 519 Anticipatory Functional Test Procedure Voltage Difference Test (ΔV) Step 1: Use BESTCOMSPlus to send the operational setting

Pagina 482

520 9424200994 Rev N Setting Value BESTCOMSPlus Screen Description Volt Pulse Interval (s) 10.0 Control, Synchronizer (25A) Sets the maximum correc

Pagina 483

9424200994 Rev N 521 Step 8: Slowly decrease the line voltage until the 25A Volt Diff digital point turns off. This should happen at 58.89 V ±1 V.

Pagina 484

522 9424200994 Rev N Step 3: Increase the phase voltage source until OUT4 begins pulsing. This should occur immediately but reaches the maximum

Pagina 485

9424200994 Rev N 523 Functional Test Report - Anticipatory ΔV Accuracy = ±2% or ±1 V, whichever is greater. Slip Freq Accuracy = ±0.01 Hz Breaker Clo

Pagina 486

524 9424200994 Rev N Transformers Aux VT Connection AN System Parameters, Sensing Transformers Sets auxiliary VT connection to AN. Nominal Phase Vo

Pagina 487

9424200994 Rev N 525 Figure 318. BESTCOMSPlus Synchronizer Screen, 25A Voltage Monitor Logic Step 4: Prepare to monitor the 25VM function operati

Pagina 488

526 9424200994 Rev N Output Test (25A Voltage Monitor) Step 1: With no voltage applied to either the Line or Auxiliary voltage sources, OUT7 sho

Pagina 489

9424200994 Rev N 527 Virtual Control Switches (43) Test Functional testing is a way to assess this protection system’s suitability for your applicati

Pagina 490

42 9424200994 Rev N Contact Inputs and Outputs BE1-11g

Pagina 491

528 9424200994 Rev N Figure 319. BESTlogicPlus Settings Step 4: Use the Metering Explorer of BESTCOMSPlus to open the Control, Virtual Switches

Pagina 492

9424200994 Rev N 529 Step 3: Use the Metering Explorer of BESTCOMSPlus to open the Control, Virtual Switches tree branch (Figure 320). Using selec

Pagina 493

530 9424200994 Rev N Virtual Control Switches (43) Test BE1-11g

Pagina 494

9424200994 Rev N 531 Logic Timers (62) Test Functional testing is a way to assess this protection system’s suitability for your application. Function

Pagina 495

532 9424200994 Rev N Figure 321. BESTlogicPlus Settings Step 3: Steps 4 through 6 will initiate the 62-1 timer by changing the 43-1 switch stat

Pagina 496

9424200994 Rev N 533 Figure 323. Pickup/Dropout Mode Step 10: (Optional.) Repeat steps 1 through 9 for 62-1, 62-2, 62-3, 62-4, 62-5, 62-6, 62-7, an

Pagina 497

534 9424200994 Rev N despite a second 43-1 OFF to ON initiate signal while the duration timer was active. Figure 324 illustrates the timing relatio

Pagina 498

9424200994 Rev N 535 Note The 43-1 switch action is performed three times in this test. To illustrate the action of the timer mode, step 4 should be

Pagina 499

536 9424200994 Rev N Note The 43-1 switch action is performed three times in this test. Follow the timing sequence to illustrate timer mode action.

Pagina 500

9424200994 Rev N 537 Figure 326. Integrating Timer Mode Latched Mode Step 1: Use BESTCOMSPlus to send the operational settings in Table 245 to th

Pagina 501

9424200994 Rev N 43 Overexcitation (24) Protection The overexcitation (24) element monitors the volts per hertz ratio and protects transformers and g

Pagina 502

538 9424200994 Rev N Figure 327. BESTlogicPlus Settings (Latched Mode) Note The 43-1 switch action is performed twice in this test. The 43-2 swit

Pagina 503

9424200994 Rev N 539 Figure 328. Latched Mode Functional Test Report Function Pass/Fail Pickup/Dropout Mode P / F One-Shot Non-Retriggerable Mod

Pagina 504

540 9424200994 Rev N Logic Timers (62) Test BE1-11g

Pagina 505

9424200994 Rev N 541 Lockout Functions (86) Test Functional testing is a way to assess this protection system’s suitability for your application. Fun

Pagina 506

542 9424200994 Rev N Step 5: Apply voltage to IN1. Verify that OUT1 closes and remains closed. Step 6: Power down the BE1-11g and verify that

Pagina 507

9424200994 Rev N 543 Breaker Control Switch (101) Test Functional testing is a way to assess this protection system’s suitability for your applicatio

Pagina 508

544 9424200994 Rev N Figure 330. BESTlogicPlus Settings Step 5: Place the 101 in the CLOSE position by using the Metering Explorer in BESTCOMSP

Pagina 509

9424200994 Rev N 545 Frequently Asked Questions (FAQ) Electrical/Connections Is the power supply polarity sensitive? No, the power supply will accept

Pagina 510

546 9424200994 Rev N How can I check the version number of my BE1-11g? The application version can be found in four different ways: One, on the Set

Pagina 511

9424200994 Rev N 547 Troubleshooting Basler microprocessor-based protection systems are similar in nature to a panel of electromechanical or solid-st

Pagina 512

44 9424200994 Rev N Trip and Reset Equations Equation 3 and Equation 4 represent the trip time and reset time for a constant V/Hz level. Normally,

Pagina 513

548 9424200994 Rev N withdrawn and any unsaved changes are lost. When activity at a port is no longer required, access should be terminated. Obtain

Pagina 514

9424200994 Rev N 549 Why don't the targets or trip LED work properly? If a protective element is tripping at the desired level, but the targets

Pagina 515

550 9424200994 Rev N Troubleshooting BE1-11g

Pagina 516

9424200994 Rev N 551 Specifications BE1-11g protection systems used in 50/60 Hz systems have the following features and capabilities. For 25 Hz opera

Pagina 517

552 9424200994 Rev N Reactive Power 5 Ampere CT Range ... –7,500 var to +7,500 var 1 Ampere CT Range

Pagina 518

9424200994 Rev N 553 Alarm Pickup Setting Range ... 0.5 to 6 V/Hz Accuracy...

Pagina 519

554 9424200994 Rev N Voltage Controller Volt Pulse Width Setting Range ... 0.1 to 5 seconds

Pagina 520

9424200994 Rev N 555 27X - Auxiliary Undervoltage Protection Pickup Setting Range ... 1 to 15

Pagina 521

556 9424200994 Rev N Directional Supervision Angle (Blinder Angle) Setting Range ... –90 to

Pagina 522

9424200994 Rev N 557 49RTD - Resistance Temperature Device Protection (Optional) Pickup Setting Range ...

Pagina 523

9424200994 Rev N 45 Programmable Alarm A 24 Volts per Hz alarm occurs during overexcitation so that corrective action can be taken before the 24 func

Pagina 524

558 9424200994 Rev N Time Delay & Control Time Setting Range ... 50 to 999 ms Accuracy.

Pagina 525

9424200994 Rev N 559 59X - Auxiliary Overvoltage Protection Pickup Setting Range ... 1 to 150

Pagina 526

560 9424200994 Rev N Blinder Angle Setting Range ... 1 to 90 degrees Accuracy...

Pagina 527

9424200994 Rev N 561 * Recognition time = 2 cycles for 0.57 > pickup, 4 cycles for 0.24 > pickup, 8 cycles for 0.08 > pickup, 16 cycles at p

Pagina 528

562 9424200994 Rev N Time Delay Setting Range ... 0 to 60,000 ms Accuracy...

Pagina 529

9424200994 Rev N 563 Terminals (CT1) IA1 ... D1, D2 IB1 ...

Pagina 530

564 9424200994 Rev N Output Contacts Make and Carry for Tripping Duty ... 30 A for 0.2 seconds per IEEE Std C37.90-2005 -

Pagina 531

9424200994 Rev N 565 Recognition Time Programmable ... 4 to 255 ms Note All timing specifica

Pagina 532

566 9424200994 Rev N Note Failure to replace the battery with Basler Electric P/N 38526 may void the warranty. Communication Ports Communication po

Pagina 533

9424200994 Rev N 567 Standards IEC Standards IEC 60068-1: Environmental Testing Part 1: General and Guidance. Temperature Test IEC 60068-2-1: Basic

Pagina 534

46 9424200994 Rev N Figure 37. Overexcitation Settings Screen Table 10. Operational Settings Setting Range Increment Unit of Measure Default Mode

Pagina 535

568 9424200994 Rev N Standards used for evaluation: • UL 508 • ISA 12.12.01 • CSA C22.2 No. 213-M1987 Warning! - EXPLOSION HAZARD Do not discon

Pagina 536

9424200994 Rev N 569 Specifications - 25 Hz Operation BE1-11g protection systems used in 25 Hz systems have the following features and capabilities.

Pagina 537

570 9424200994 Rev N Reactive Power 5 Ampere CT Range ... –7,500 var to +7,500 var 1 Ampere CT Range

Pagina 538

9424200994 Rev N 571 Alarm Pickup Setting Range ... 0.5 to 6 V/Hz Accuracy...

Pagina 539

572 9424200994 Rev N Voltage Controller Volt Pulse Width Setting Range ... 0.1 to 5 seconds

Pagina 540

9424200994 Rev N 573 27X - Auxiliary Undervoltage Protection Pickup Setting Range ... 1 to 15

Pagina 541

574 9424200994 Rev N Directional Supervision Angle (Blinder Angle) Setting Range ... –90 to

Pagina 542

9424200994 Rev N 575 49RTD - Resistance Temperature Device Protection (Optional) Pickup Setting Range ...

Pagina 543

576 9424200994 Rev N Time Delay & Control Time Setting Range ... 50 to 999 ms Accuracy.

Pagina 544

9424200994 Rev N 577 59X - Auxiliary Overvoltage Protection Pickup Setting Range ... 1 to 150

Pagina 545

9424200994 Rev N 47 Figure 38. Time Shown on Vertical Axis Figure 39. Time Shown on Horizontal Axis Volt/Hz Characteristic1.010.0100.01000.0100%

Pagina 546

578 9424200994 Rev N Blinder Angle Setting Range ... 1 to 90 degrees Accuracy...

Pagina 547

9424200994 Rev N 579 * Recognition time = 2 cycles for 0.57 > pickup, 4 cycles for 0.24 > pickup, 8 cycles for 0.08 > pickup, 16 cycles at p

Pagina 548

580 9424200994 Rev N Time Delay Setting Range ... 0 to 60,000 ms Accuracy...

Pagina 549

9424200994 Rev N 581 Time Curve Characteristics This chapter provides time curve information for the inverse overcurrent (51), under/overvoltage (27/

Pagina 550

582 9424200994 Rev N Curve Selection Curve Name Trip Characteristic Constants Reset ∗ A B C N K R I1 CO Inverse Time 8.9341 0.17966 1 2.0938 0.028

Pagina 551

9424200994 Rev N 583 Table 252. Characteristic Curve Cross-Reference Curve Curve Name Similar To S1 CO Short Inverse ABB CO-2 S2 IAC Short Inverse GE

Pagina 552

584 9424200994 Rev N Basler Electric protection systems have a maximum time dial setting of 9.9. The Basler Electric equivalent time dial setting f

Pagina 553

9424200994 Rev N 585 The K factor gives the time that a generator can withstand 1 per unit negative sequence current. For example, with a K factor of

Pagina 554

586 9424200994 Rev N Figure 334. Time Characteristic Curve S1, Short Inverse (Similar to ABB CO-2) Time Curve Characteristics BE1-11g

Pagina 555

9424200994 Rev N 587 Figure 335. Time Characteristic Curve S2, Short Inverse (Similar To GE IAC-55) BE1-11g Time Curve Characteristics

Pagina 556

iv 9424200994 Rev N Frequency (81) Protection ...

Pagina 557

48 9424200994 Rev N Assuming a Vnom of 69.3 Vpn, 1 pu volts/hertz = (69.3 * √3) / 60 = 2.00. Using IEEE Std C37.102-2006 - IEEE Guide for AC Genera

Pagina 558

588 9424200994 Rev N Figure 336. Time Characteristic Curve A, Standard Inverse (BS 142) Time Curve Characteristics BE1-11g

Pagina 559

9424200994 Rev N 589 Figure 337. Time Characteristic Curve A1, Inverse (IEC 60255-151 Ed. 1) BE1-11g Time Curve Characteristics

Pagina 560

590 9424200994 Rev N Figure 338. Time Characteristic Curve I1, Inverse Time (Similar to ABB CO-8) Time Curve Characteristics BE1-11g

Pagina 561

9424200994 Rev N 591 Figure 339. Time Characteristic Curve I2, Inverse Time (Similar to GE IAC-51) BE1-11g Time Curve Characteristics

Pagina 562

592 9424200994 Rev N Figure 340. Time Characteristic Curve M, Moderately Inverse (Similar to ABB CO-7) Time Curve Characteristics BE1-11g

Pagina 563

9424200994 Rev N 593 Figure 341. Time Characteristic Curve D1, Moderately Inverse (IEC 60255-151 Ed. 1) 0.010.101.0010.00100.001000.001 10 100MUL

Pagina 564

594 9424200994 Rev N Figure 342. Time Characteristic Curve L1, Long Inverse (Similar to ABB CO-5) Time Curve Characteristics BE1-11g

Pagina 565

9424200994 Rev N 595 Figure 343. Time Characteristic Curve L2, Long Inverse (Similar To GE IAC-66) BE1-11g Time Curve Characteristics

Pagina 566

596 9424200994 Rev N Figure 344. Time Characteristic Curve G, Long Time Inverse (BS 142) Time Curve Characteristics BE1-11g

Pagina 567

9424200994 Rev N 597 Figure 345. Time Characteristic Curve V1, Very Inverse (Similar to ABB CO-9) BE1-11g Time Curve Characteristics

Pagina 568

9424200994 Rev N 49 Sync-Check (25) Protection The sync-check (25) element provides breaker closing supervision by comparing the voltage magnitude, a

Pagina 569

598 9424200994 Rev N Figure 346. Time Characteristic Curve V2, Very Inverse (Similar to GE IAC-53) Time Curve Characteristics BE1-11g

Pagina 570

9424200994 Rev N 599 Figure 347. Time Characteristic Curve B, Very Inverse (BS 142) BE1-11g Time Curve Characteristics

Pagina 571

600 9424200994 Rev N Figure 348. Time Characteristic Curve B1, Very Inverse (IEC 60255-151 Ed. 1) Time Curve Characteristics BE1-11g

Pagina 572

9424200994 Rev N 601 Figure 349. Time Characteristic Curve E3, Very Inverse (IEC 60255-151 Ed. 1) 0.010.101.0010.00100.001000.001 10 100MULTIPLES

Pagina 573

602 9424200994 Rev N Figure 350. Time Characteristic Curve E1, Extremely Inverse (Similar to ABB CO-11) Time Curve Characteristics BE1-11g

Pagina 574

9424200994 Rev N 603 Figure 351. Time Characteristic Curve E2, Extremely Inverse (Similar to GE IAC-77) BE1-11g Time Curve Characteristics

Pagina 575

604 9424200994 Rev N Figure 352. Time Characteristic Curve C, Extremely Inverse (BS 142) Time Curve Characteristics BE1-11g

Pagina 576

9424200994 Rev N 605 Figure 353. Time Characteristic Curve C1, Extremely Inverse (IEC 60255-151 Ed. 1) BE1-11g Time Curve Characteristics

Pagina 577

606 9424200994 Rev N Figure 354. Time Characteristic Curve F1, Extremely Inverse (IEC 60255-151 Ed. 1) 0.010.101.0010.00100.001000.001 10 100MU

Pagina 578

9424200994 Rev N 607 Figure 355. Time Characteristic Curve D, Definite Time (Similar To ABB CO-6) BE1-11g Time Curve Characteristics

Pagina 579

50 9424200994 Rev N Terminals Va (C13), Vb (C14), and Vc (C15) are connected in parallel. The single-phase signal is connected between the parallel

Pagina 580

608 9424200994 Rev N Figure 356. 46 Time Characteristic Curve NOTE: Curves are shown as extending farther to the left than they will in practice.

Pagina 581

9424200994 Rev N 609 Under/Overvoltage (27/59) The 27 and 59 elements have independent user defined definite and inverse time delays. The inverse tim

Pagina 582

610 9424200994 Rev N Figure 357. Undervoltage (27) Inverse Time Curve 0.101.0010.00100.000 1TIME IN SECONDS MULTIPLES OF PICKUP 9.99876543210.5

Pagina 583

9424200994 Rev N 611 Overvoltage (59) Inverse Time Curve The overvoltage inverse time curve is defined by Equation 35 and shown in Figure 358. =

Pagina 584

612 9424200994 Rev N Figure 358. Overvoltage (59) Inverse Time Curve 0.101.0010.00100.001 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2TIME IN SECONDS

Pagina 585

9424200994 Rev N 613 Overexcitation (24) General The inverse time curves for the overexcitation (24) element are defined below. Equation 36 and Equat

Pagina 586

614 9424200994 Rev N Figure 359. V/Hz Characteristic (M-1)^0.5 – Time on Vertical Axis Figure 360. V/Hz Characteristic (M-1)^0.5 – Time on Horiz

Pagina 587

9424200994 Rev N 615 Figure 361. V/Hz Characteristic (M-1)^1 – Time on Vertical Axis Figure 362. V/Hz Characteristic (M-1)^1 – Time on Horizontal

Pagina 588

616 9424200994 Rev N Figure 363. V/Hz Characteristic (M-1)^2 – Time on Vertical Axis Figure 364. V/Hz Characteristic (M-1)^2 – Time on Horizonta

Pagina 589

9424200994 Rev N 617 RTD Module The RTD (Resistance Temperature Detector) module is an optional remote device that provides RTD inputs, analog inputs

Pagina 590

9424200994 Rev N 51 Phase VT Connection Phase Rotation Aux VT Connection Secondary Phase Voltage (Phase-Neutral) Secondary Aux Voltage Angle Compensa

Pagina 591

618 9424200994 Rev N Mounting RTD modules are contained in a potted plastic case and may be mounted in any convenient position using UNC ¼-20 or eq

Pagina 592

9424200994 Rev N 619 Connections RTD module connections are dependent on the application. Incorrect wiring may result in damage to the module. Note

Pagina 593

620 9424200994 Rev N Figure 366. Input and Output Terminals Table 256. Input and Output Terminals Connector Description TB1 Operating Power and Al

Pagina 594

9424200994 Rev N 621 Figure 367. Analog Inputs - Voltage Input Connections Figure 368. Analog Inputs - Current Input Connections External RTD Input

Pagina 595

622 9424200994 Rev N Figure 370. External Three-Wire RTD Input Connections RTD Module Communications Setup Procedure Communication between the BE1

Pagina 596

9424200994 Rev N 623 5. Open the RTD Module plugin in BESTCOMSPlus. 6. Pull down the Communication menu and select New Connection  RTD Module. The

Pagina 597

624 9424200994 Rev N Figure 372. Procedure 2 Connect to RTD Module 1. Connect an Ethernet cable directly between the PC and RTD module. 2. Apply

Pagina 598

9424200994 Rev N 625 10. Click Send to Device. A password is required. The default password is “OEM”. Click Close. 11. Click Cancel on the Device Dis

Pagina 599

626 9424200994 Rev N Figure 373. BESTCOMSPlus Select Language Screen The BESTCOMSPlus splash screen is shown for a brief time. See Figure 374. Fi

Pagina 600

9424200994 Rev N 627 Figure 376. RTD Module Connection Screen Wait until scanning is complete. See Figure 377. Figure 377. Scanning for Connected D

Pagina 601

52 9424200994 Rev N If the 60FL element trip logic is true and Block Phase/V1 is enabled, all functions that use the phase voltage are blocked. See

Pagina 602

628 9424200994 Rev N The Configure - RTD Module screen shown in Figure 379 appears. The BE1-11g uses the Device Address to communicate with the con

Pagina 603

9424200994 Rev N 629 screen is found by selecting Activate Device from the Tools pull-down menu of the BESTCOMSPlus main screen. Device Info Informat

Pagina 604

630 9424200994 Rev N Figure 383. Login Screen Enter the Password and then click the Log In button. The default password is “OEM”. The Device Secur

Pagina 605

9424200994 Rev N 631 Figure 385. Module 1 Input #1 Screen Table 257 summarizes the configuration settings for remote analog inputs. Table 257. Confi

Pagina 606

632 9424200994 Rev N Figure 386. Module 1 Output #1 Screen Table 258 summarizes the configuration settings for remote analog outputs. Table 258. C

Pagina 607

9424200994 Rev N 633 Figure 387. RTD Type Selection Screen Use the Settings Explorer to open the Programmable Outputs, Remote RTD, RTD Block Configu

Pagina 608

634 9424200994 Rev N Maximum Lead Length ... 150 feet (4.25 km) with 22 AWG (0.326 mm2) wire Sensing Current Level ... 2.5

Pagina 609

9424200994 Rev N 635 IEC 60255-5: Electrical Insulation Tests for Electrical Relays. Dielectric Test and Impulse Test IEC 60255-6: Electrical Relay

Pagina 610

636 9424200994 Rev N expected to provide long-term operation in a rugged environment. Note that the vibration and temperature extremes listed in th

Pagina 611

9424200994 Rev N 637 Digital Points The status of all BE1-11g digital points is displayed in the Metering Explorer of BESTCOMSPlus® under Status, Dig

Pagina 612

9424200994 Rev N 53 Figure 43. Sync-Check Settings Screen Table 13. Operational Settings Setting Range Increment Unit of Measure Default Mode Disabl

Pagina 613

638 9424200994 Rev N Name Number 27X-3 Pickup 83 27X-3 Trip 84 27X-3 V1 89 27X-3 V2 86 27X-4 3RD 96 27X-4 3V0 93 27X-4 AUX 95 27X-4 Block 90 27X-4

Pagina 614

9424200994 Rev N 639 Name Number 49RTD-1 RTD 2-7 1043 49RTD-1 RTD 2-8 1044 49RTD-1 RTD 2-9 1045 49RTD-1 Trip 1024 49RTD-10 Block 1884 49RTD-10 Pickup

Pagina 615

640 9424200994 Rev N Name Number 49RTD-14 RTD 1-6 2000 49RTD-14 RTD 1-7 2001 49RTD-14 RTD 1-8 2002 49RTD-14 RTD 1-9 2003 49RTD-14 RTD 2-1 2007 49RT

Pagina 616

9424200994 Rev N 641 Name Number 49RTD-5 RTD 2-8 1152 49RTD-5 RTD 2-9 1153 49RTD-5 Trip 1132 49RTD-6 Block 1157 49RTD-6 Pickup 1158 49RTD-6 RTD 1-1 1

Pagina 617

642 9424200994 Rev N Name Number 50-1 C 171 50-1 IND GND 174 50-1 Neg SEQ 172 50-1 Pickup 167 50-1 Pos SEQ 181 50-1 Prevent Config Option Change 18

Pagina 618

9424200994 Rev N 643 Name Number 51-1 67T IND GND 300 51-1 67T Neg SEQ 298 51-1 67T Pos SEQ 302 51-1 67T Residual 299 51-1 A 289 51-1 B 290 51-1 Bloc

Pagina 619

644 9424200994 Rev N Name Number 51-7 67T Pos SEQ 422 51-7 67T Residual 419 51-7 A 409 51-7 B 410 51-7 Block 406 51-7 C 411 51-7 IND GND 414 51-7 N

Pagina 620

9424200994 Rev N 645 Name Number 62-7 616 62-7 Block 614 62-7 Initiate 615 62-8 619 62-8 Block 617 62-8 Initiate 618 67 NEG SEQ DIR F 157 67 NEG SEQ

Pagina 621

646 9424200994 Rev N Name Number Analog Input Protection 4 Pickup 984 Analog Input Protection 4 Trip 985 Analog Input Protection 5 990 Analog Input

Pagina 622

9424200994 Rev N 647 Name Number GGIO-CTL1 Oper01Alarm 1569 GGIO-CTL1 Oper01Default 1568 GGIO-CTL1 Oper02 1570 GGIO-CTL1 Oper02Alarm 1572 GGIO-CTL1 O

Pagina 623

54 9424200994 Rev N Sync-Check (25) Protection BE1-11g

Pagina 624

648 9424200994 Rev N Name Number GGIO-CTL3 Oper10 1690 GGIO-CTL3 Oper10Alarm 1692 GGIO-CTL3 Oper10Default 1691 GGIO-CTL3 Oper11 1693 GGIO-CTL3 Oper

Pagina 625

9424200994 Rev N 649 Name Number INDGGIO4_IND06 1303 INDGGIO4_IND07 1304 INDGGIO4_IND08 1305 INDGGIO4_IND09 1306 INDGGIO4_IND10 1307 INDGGIO4_IND11 1

Pagina 626

650 9424200994 Rev N Name Number Programmable Alarm 7 755 Programmable Alarm 8 756 Programmable Alarm 9 757 Real Time Clock 730 Relay Alarms 793 Re

Pagina 627

9424200994 Rev N 651 Revision History Table 260 provides a historical summary of the changes made to the BE1-11g hardware. Application firmware chang

Pagina 628

652 9424200994 Rev N Table 261. Application Firmware Revision History Firmware Version and Date Change 1.01.00, Apr-09 • Initial release 1.02.00,

Pagina 629

9424200994 Rev N 653 Firmware Version and Date Change 2.07.00, Nov-13 • Made alarms available in BESTlogicPlus • Expanded Target Reset logic point

Pagina 630

654 9424200994 Rev N Software Version and Date Change 2.05.00, Jul-09 • Updated Basler Electric Device Package Uploader screen • Changed 40Q pick

Pagina 631

9424200994 Rev N 655 Software Version and Date Change 3.01.01, Nov-12 • Added Delta/Wye Compensation Enable setting on the Distance (21) settings sc

Pagina 632

656 9424200994 Rev N Manual Revision and Date Change E, Mar-11 • Replaced Figure 3-13, Auto Export Metering (Added Filter button on screen) • Rep

Pagina 633

9424200994 Rev N 657 Manual Revision and Date Change N, Sep-14 • Added Conformal Coating to Option 2 in Figures 1 and 264 • Added power supply burd

Pagina 634

9424200994 Rev N 55 Phase Undervoltage (27P) Protection Five phase undervoltage (27P) elements monitor the sensing voltage applied to the BE1-11g. An

Pagina 635

658 9424200994 Rev N Revision History BE1-11g

Pagina 637

12570 State Route 143 Highland IL 62249-1074 USA Tel: +1 618.654.2341 Fax: +1 618.654.2351 email: [email protected] P.A.E. Les Pins 67319 Wasselonne

Pagina 638

56 9424200994 Rev N Trip The Trip output becomes true when an undervoltage pickup condition persists for the duration of the element Time Delay set

Pagina 639

9424200994 Rev N 57 Operational Settings Phase undervoltage element operational settings are configured on the Undervoltage (27P) settings screen (Fi

Pagina 640

9424200994 Rev N v Out of Step (78OOS) Protection ...

Pagina 641

58 9424200994 Rev N Phase Undervoltage (27P) Protection BE1-11g

Pagina 642

9424200994 Rev N 59 Auxiliary Undervoltage (27X) Protection Four auxiliary undervoltage (27X) elements monitor the phase and auxiliary voltage applie

Pagina 643

60 9424200994 Rev N parameter set to AB, for example, will display the metering data as AB in fault records and display the pickup setting as Vpp i

Pagina 644

9424200994 Rev N 61 Element Blocking Fuse Loss The fuse loss (60FL) element of the BE1-11g can be used to block 27X protection when fuse loss or loss

Pagina 645

62 9424200994 Rev N Figure 47. Auxiliary Undervoltage Settings Screen Table 18. Operational Settings Setting Range Increment Unit of Measure Defau

Pagina 646

9424200994 Rev N 63 Negative-Sequence Voltage (47) Protection Negative-sequence voltage protection is included as a mode of the 27X (Auxiliary Underv

Pagina 647

64 9424200994 Rev N Negative-Sequence Voltage (47) Protection BE1-11g

Pagina 648

9424200994 Rev N 65 Phase Overvoltage (59P) Protection Four phase overvoltage (59P) elements monitor the sensing voltage applied to the BE1-11g. An e

Pagina 649

66 9424200994 Rev N Trip The Trip output becomes true if an overvoltage pickup condition persists for the duration of the element Time Delay settin

Pagina 650

9424200994 Rev N 67 Figure 49. Overvoltage Settings Screen Table 20. Operational Settings Setting Range Increment Unit of Measure Default Mode Disab

Pagina 651

vi 9424200994 Rev N Alarms ...

Pagina 652

68 9424200994 Rev N Phase Overvoltage (59P) Protection BE1-11g

Pagina 653

9424200994 Rev N 69 Auxiliary Overvoltage (59X) Protection Four auxiliary overvoltage (59X) elements monitor the phase and auxiliary voltage applied

Pagina 654

70 9424200994 Rev N pickup setting as Vpp in BESTCOMSPlus. See Table 21 for a full list of possible settings. The Aux VT Connection parameter is fo

Pagina 655

9424200994 Rev N 71 element Block input to the desired logic in BESTlogicPlus. When the element is initially selected from the Elements view, the def

Pagina 656

72 9424200994 Rev N Table 23. Operational Settings Setting Range Increment Unit of Measure Default Mode* Disabled, 3V0, V1, V2, Vx Fundamental, Vx

Pagina 657

9424200994 Rev N 73 Stator Ground (64G) Protection The BE1-11g provides ground protection for 100% of the stator winding on high-impedance, grounded

Pagina 658

74 9424200994 Rev N Stator Ground (64G) Protection BE1-11g

Pagina 659

9424200994 Rev N 75 Vector Jump (78V) Protection The vector jump (78V) element protects the generator by disconnecting it from the grid when a loss o

Pagina 660

76 9424200994 Rev N If the 60FL element trip logic is true and Block Phase/V1 is enabled, all functions that use the phase voltage are blocked. See

Pagina 661

9424200994 Rev N 77 Table 25. Operational Settings Setting Range Increment Unit of Measure Default Mode Disabled or Enabled n/a n/a Disabled Source P

Pagina 662

9424200994 Rev N vii Settings File Management ...

Pagina 663

78 9424200994 Rev N Vector Jump (78V) Protection BE1-11g

Pagina 664

9424200994 Rev N 79 Frequency (81) Protection Eight frequency (81) elements monitor the frequency of the sensing voltage applied to the BE1-11g. An e

Pagina 665

80 9424200994 Rev N Pickup and Trip The Pickup output occurs first, followed by the Trip output. Pickup The Pickup output becomes true when the mea

Pagina 666

9424200994 Rev N 81 Sensing Source Frequency ROC protection can be applied to the voltage sensed at the BE1-11g phase VT input or auxiliary VT (Vx) i

Pagina 667

82 9424200994 Rev N Logic Connections Frequency element logic connections are made on the BESTlogicPlus screen in BESTCOMSPlus. The frequency eleme

Pagina 668

9424200994 Rev N 83 Setting Range Increment Unit of Measure Default Voltage Inhibit 0 or 15 to 250 0.1 volts* 20 81ROC Over Frequency Inhibit 15 to 7

Pagina 669

84 9424200994 Rev N Frequency (81) Protection BE1-11g

Pagina 670

9424200994 Rev N 85 Negative-Sequence Overcurrent (46) Protection Negative-sequence overcurrent protection is included as a mode of the 50 (Instantan

Pagina 671

86 9424200994 Rev N Figure 57. Sequence Components for an A-B Fault Coordination Settings The 51-x negative-sequence settings should be checked fo

Pagina 672

9424200994 Rev N 87 Instantaneous Overcurrent (50) Protection Six instantaneous overcurrent (50) elements monitor the current applied to the BE1-11g.

Commenti su questo manuale

Nessun commento