Table 115. CT Input Circuit Settings for Non-transformer or Wye-only Application
Transformer
Connection
CT Input
Connection
BE1-11g Settings
Compensation Applied
TX
CT
Phase
Rotation
N/A
WYE
NA
WYE
WYE
NONE
DAB
NA
DAB
WYE
NONE
DAC
NA
DAC
WYE
NONE
All WYE
All WYE
WYE
WYE
WYE
NONE
Special case where all transformer windings and all CTs are connected in wye.
Table 116. CT Input Circuit Settings 1 for Delta/Wye Circuit Applications
Transformer
Connection
CT Input
Connection
BE1-11g Settings
Compensation Applied
TX CT Phase Rotation
WYE
WYE
WYE
WYE
DAB for DAB
connections
DAC for DAC
connections
NONE
WYE
DAB WYE DAB WYE NONE
WYE DAC WYE DAC WYE NONE
DAB WYE DAB WYE WYE NONE
DAC WYE DAC WYE WYE NONE
ZAB WYE ZAB WYE WYE NONE