Basler-electric BE1-11g Manuale Utente Pagina 536

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 672
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 535
524 9424200994 Rev N
Transformers
Aux VT
Connection
AN
System Parameters, Sensing
Transformers
Sets auxiliary VT
connection to AN.
Nominal Phase
Voltage
100 V
System Parameters, Power
System
Sets nominal phase voltage
to 100 V.
Nominal Aux
Voltage
100 V
System Parameters, Power
System
Sets nominal auxiliary
voltage to 100 V.
Element Mode
PLL or
Anticipatory
Control, Synchronizer (25A)
Enables the 25A function.
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in
Figure 317.
Blocking is disabled.
25A is initiated.
OUT7 closes for voltage monitor criteria met.
Event recording is enabled.
Figure 317. BESTlogicPlus Settings 3 (25A)
Step 3: Use BESTCOMSPlus to open the Control, Synchronizer (25A) screen and send the test settings
in Table 238 to the BE1-11g.
Table 238. Time Pickup Test Settings (25VM)
Setting Value Description
25 Voltage Monitor Live
Voltage
90%
Sets live voltage to 90 V (90% of nominal, nominal
= 100 V).
25 Voltage Monitor
Dead Voltage
55%
Sets dead voltage to 55 V (55% of nominal, nominal
= 100 V).
25 Voltage Monitoring
Drop Out Delay
0 Sets drop out delay to 0.
25 Voltage Monitor
Logic
Check boxes as
shown in Figure 318.
Enable: Dead Line/Dead Aux, Dead Line/Live Aux,
Live Line/Dead Aux.
Synchronizer (25A) Test BE1-11g
Vedere la pagina 535
1 2 ... 531 532 533 534 535 536 537 538 539 540 541 ... 671 672

Commenti su questo manuale

Nessun commento