240 9424200994 Rev N
Block V2 Voltage Elements
All functions that use the negative-sequence voltage (V2)
measurement are blocked when the 60FL logic is true. (27X, 59X -
Block Power/Power Factor
Elements
All functions that use the power measurements are blocked when
the 60FL logic is true. (32)
All functions that use the impedance measurement are blocked
when the 60FL logic is true. (21 and 40Z)
When enabled, breaker status is ignored.
Fuse Loss (60FL) BE1-11g